UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)
Mains Input Electrical Specifications
Item
Rated voltage (line
voltage)
Rated current
(capacity: 600 kVA)
Power system
Voltage range
Rated frequency
Frequency range
Power factor
Harmonic current
Overvoltage category
Bypass Input Electrical Specifications
Item
Rated voltage (line
voltage)
Rated current
(capacity: 600 kVA)
Power system
Rated frequency
Issue 02 (2024-01-05)
Specifications
380 V AC
1115 A
Three-phase four-wire + PE
● 0–30°C: not derated at 323–485 V, derated from 100% load to 45%
load at 323–191 V, and derated from 45% load to 35% load at 191–
138 V
● 30–40°C: not derated at 342–485 V, derated from 100% load to 45%
load at 342–191 V, and derated from 45% load to 35% load at 191–
138 V
50/60 Hz
40–70 Hz
● > 0.99 (100% load)
● > 0.98 (50% load)
● > 0.94 (30% load)
● THDi < 9% (30% linear load), THDi < 6% (50% linear load), THDi <
3% (100% linear load)
● THDi < 11% (30% non-linear load), THDi < 8% (50% non-linear
load), THDi < 5% (100% non-linear load)
The preceding specifications can be met only when the following
conditions are met:
● One power source
● Input THDv < 2%
OVC II
Specifications
380 V AC
912 A
Three-phase four-wire + PE
50/60 Hz
Copyright © Huawei Digital Power Technologies Co., Ltd.
400 V AC
1059 A
400 V AC
866 A
3 Technical Specifications
415 V AC
1021 A
415 V AC
835 A
50