UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)
Parameter
Odd-order harmonic
compensation setting
ECO voltage range
Step 3 (Optional) If you set S-ECO mode in bypass mode, manually start the UPS
inverter.
After the inverter is started, the UPS still supplies power through the bypass, and
the inverter is standby. When the bypass is abnormal, the UPS transfers to inverter
mode immediately. If the inverter is not started, the UPS stops supplying power
when the bypass is abnormal, and the system may power off.
Figure 5-6 S-ECO system status (VFI)
Issue 02 (2024-01-05)
Description
When Working mode is set to
S-ECO and Harmonic
compensation is set to Enable,
you can enable or disable odd-
order harmonic compensation.
In S-ECO or ECO mode, when
the difference between the
bypass voltage and the rated
voltage is greater than the
specified value, the system
determines that the ECO
voltage is abnormal and
transfers to inverter mode.
NO TE
If the S-ECO mode is set when the UPS works in inverter mode, the UPS transfers to the S-
ECO mode 4 minutes after the setting is complete and the conditions are met.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Single UPS Commissioning
Default Value
User-defined
±5%
Value Range
-
±5%, ±6%, ±7%,
±8%, ±9%, ±10%