User Manual (FusionPower6000)
Table 2-9 Pin definitions for the COM1 port
Appearance
RJ45 (8-pin)
RJ11 (6-pin)
Table 2-10 Pin definitions for the COM2, FE, and RS485 ports
Appearance
Issue 02 (2024-01-05)
Pin
COM1 Port
1
RS485_R+
2
RS485_R–
3
12V_PORT
4
RS485_T+
5
RS485_T–
6
-
7
-
8
GND
1
GND
2
-
3
RS485_R–
4
RS485_R+
5
-
6
12V_PORT
Pin
COM2 Port
1
RS485_R+
2
RS485_R–
3
-
4
RS485_T+
5
RS485_T–
6
GND
7
CAN_H
8
CAN_L
Copyright © Huawei Digital Power Technologies Co., Ltd.
FE Port
RS485
Port
RJ_TX+
RS485_T
+
RJ_TX–
RS485_T–
RJ_RX+
-
-
RS485_R
+
-
RS485_R–
RJ_RX-
GND
-
-
-
-
2 Product Overview
Remarks
If cables need to be prepared
for the COM2 and RS485 ports
onsite, use any of the
following methods:
● Connect pin 1 and pin 2.
Pin 1 connects to RS485+
and pin 2 connects to
RS485–.
● Connect pin 4 and pin 5.
Pin 4 connects to RS485+
and pin 5 connects to
RS485–.
● Connect pins 1, 2, 4, and 5.
Twist cables to pin 1 and
pin 4 into one cable and
then connect it to RS485+.
Twist cables to pin 2 and
pin 5 into one and then
connect it to RS485–.
44