General Requirements
This is a category C3 battery product for commercial and industrial application in
the second environment − installation restrictions or additional measures may be
needed to prevent disturbances.
To ensure battery safety and battery management accuracy, use batteries provided
by the Company. The Company is not responsible for any faults of batteries
provided by other vendors.
Issue 02 (2024-01-05)
Batteries are not transported, stored, or charged according to the
instructions in the user manual.
Instructions from the Company are not followed during battery relocation
or reinstallation.
NO TICE
NO TICE
Before installing, operating, and maintaining batteries, read the battery
vendor's instructions and comply with their requirements. The safety
precautions specified in this document are highly important and require
special attention. For additional safety precautions, see the instructions
provided by the battery vendors.
Use batteries within the specified temperature range. When the ambient
temperature of the batteries is lower than the allowed range, do not charge
the batteries to prevent internal short circuits caused during low-temperature
charging.
Do not reversely connect the positive and negative battery terminals.
Otherwise, a battery alarm will be generated and batteries may be damaged.
To prevent dust buildup that may damage the equipment, install battery
modules after dust-prone operations in the equipment room are completed.
Before unpacking batteries, check whether the packaging is intact. Do not use
batteries with damaged packaging. If any damage is found, notify the carrier
and manufacturer immediately.
Do not unpack batteries in an environment where the temperature and
humidity are uncontrollable. Before unpacking batteries, keep them still for 24
hours in an environment where the temperature and humidity are under
control.
In an indoor scenario, you are advised to power on a battery within seven
days after unpacking. If the battery cannot be powered on in time, put it in
the original packing case and place it in a dry indoor environment without
corrosive gas.
Do not use a damaged battery (such as damage caused when a battery is
dropped, bumped, bulged, or dented on the enclosure), because the damage
may cause electrolyte leakage or flammable gas release. In the case of
electrolyte leakage or structural deformation, contact the installer or
Copyright © Huawei Digital Power Technologies Co., Ltd.