Context
The following information can be exported: historical alarms, active alarms,
performance data, operation logs, e-labels, and fault information.
LCD
Insert a USB flash drive into the USB port on the monitoring module. On the LCD,
choose System Status > Maintenance > USB Operations > Fault Data and
download the required data.
Figure 9-2 Exporting data
WebUI
Issue 02 (2024-01-05)
Exporting fault information
Choose Maintenance > Fault Information, set Encryption password for
export, click Export Fault Information, and specify a path to save the
exported data.
Figure 9-3 Export Fault Information
Exporting e-labels
Choose Maintenance > E-Label, click Export All in the lower left corner, and
specify a path to save the exported data.
Exporting historical data
Choose Query > Export Data and set Encryption password for export. In the
Data type drop-down list box, select All, Historical Alarm, Active Alarm,
Performance Data, or Operation Data. Click Export historical data and
specify a path to save the exported data.