Item
Frequency range
Input mode
Overvoltage category
Battery Electrical Specifications
The UPS supports the SmartLi. For details about related parameters, see the
SmartLi user manual.
Item
Battery type
Battery voltage (lead-
acid battery)
Nominal discharge
current (lead-acid
battery)
Issue 02 (2024-01-05)
Specifications
50/60 Hz±6 Hz (adjustable with a tolerance of 0.5–6 Hz, ±2 Hz by
default)
The mains input and bypass input share a power source (by default) or
use different power sources.
OVC II
NO TICE
Specifications
● Lead-acid battery (VRLA)
● SmartLi: For the supported version, contact technical support.
360–600 V DC
● 12 V batteries (30–50 batteries, 0 by default)
– 40–50 batteries: not derated
– 38–39 batteries: derated to 90%
– 34–37 batteries: derated to 80%
– 30–33 batteries: derated to 70%
● 2 V batteries (180–300 batteries, 0 by default)
– 240–300 batteries: not derated
– 228–239 batteries: derated to 90%
– 204–227 batteries: derated to 80%
– 180–203 batteries: derated to 70%
NOTE
● The number of batteries is 0 by default and needs to be set based on site
requirements. Batteries have no neutral wire, and an odd number of batteries
are supported.
● When the UPS works in normal mode, if the actual load rate exceeds the
threshold that could trigger battery derating, an output overload alarm is
generated.
1330 A (480 V, forty 12 V batteries in standard configuration)
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Technical Specifications
51