Huawei FusionPower6000 UPS5000-H-600 kVA-FT User Manual page 64

Hide thumbs Also See for FusionPower6000 UPS5000-H-600 kVA-FT:
Table of Contents

Advertisement

UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)
Output Electrical Specifications
Item
Rated voltage
Current
Power system
Frequency
THDv
Power factor
Transfer time
Output voltage
imbalance
Inverter overload
capability
Inverter output short-
circuit capability
Bypass overload
capability
Issue 02 (2024-01-05)
Specifications
200 V AC
866 A
Three-phase four-wire + PE
● In normal mode, the frequency is synchronous with the bypass input
frequency.
● In battery mode, the frequency is 50/60 Hz with a tolerance of
±0.05%.
● Linear load THDv < 2% (50–100% load balancing)
● Non-linear load THDv < 5% (50–100% load balancing)
1
● Double conversion mode: uninterrupted transfer 0 ms; interrupted
transfer ≤ 5 ms
● Voltage imbalance: ±1%
● Phase imbalance: 120±1° (balanced load and unbalanced load)
Inverter overload capability for top airflow:
● 100% < load ≤ 110%: transfers to bypass mode after 60 min or longer
● 110% < load ≤ 125%: transfers to bypass mode after 10 min or longer
(ambient temperature ≤ 30°C)
● 110% < load ≤ 125%: transfers to bypass mode after 1 min or longer
(ambient temperature > 30°C)
● 125% < load ≤ 150%: transfers to bypass mode after 1 min or longer
(ambient temperature ≤ 30°C)
● 125% < load ≤ 150%: transfers to bypass mode after 20 seconds or
longer (ambient temperature > 30°C)
● Load > 150%: transfers to bypass mode after 200 ms or longer
If the initial load rate is less than 40%, twice the rated current can be
tolerated for 300 ms (that is, the short-circuit current RMS is 2176 A) in
the case of inverter output short-circuit.
● At 25°C: runs continuously at 125% load; generates only alarms and
depends on overtemperature protection at 150% load.
● If the load of the bypass single-phase or three-phase is 150%–200%,
the bypass will be shut down in 5 min, and the hardware depends on
overtemperature protection. If the load of the bypass single-phase or
three-phase is greater than 200%, the bypass will be shut down in 1
min, and the hardware depends on overtemperature protection.
● If the load exceeds 1000%, the bypass can keep working for 100 ms.