UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)
Procedure
Step 1 On the LCD, choose System Info > Settings > System Settings and set Working
mode to ECO. The information indicating that the UPS works in ECO mode is
displayed on the LCD.
Step 2 Set the ECO voltage range.
Figure 5-9 ECO specifications
Step 3 (Optional) If you set ECO mode when the UPS is in bypass mode, manually start
the UPS inverter.
After the inverter is started, the UPS still works in bypass mode, and the inverter is
on standby. When the bypass is abnormal, the UPS transfers to inverter mode
immediately. If the inverter is not started, the UPS stops supplying power when
the bypass is abnormal, and the system may power off.
Figure 5-10 System status in ECO mode
----End
Issue 02 (2024-01-05)
NO TE
If the ECO mode is set when the UPS works in inverter mode, the UPS transfers to the ECO
mode 4 minutes after the setting is complete and the conditions are met.
NO TICE