Procedure
Step 1 Set the mode. On the LCD, choose System Info > Settings > System Settings and
set Working mode to S-ECO. The information indicating that the UPS works in S-
ECO mode is displayed on the LCD.
Step 2 Set parameters.
Figure 5-3 S-ECO mode parameters 1
Figure 5-4 S-ECO mode parameters 2
Issue 02 (2024-01-05)
The S-ECO mode requires the support of the hardware of both the power
module and bypass module. If the system runs in S-ECO mode but the
hardware is changed and does not support it, the system displays the
message "The current hardware does not support S-ECO. The system will
work in ECO mode." After you click OK, the system transfers to the ECO mode
(5 ms interruption may occur during the transfer to the ECO mode). If the
hardware supports this mode but the prerequisites are not met, the system
works in normal mode.