UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)
Figure 5-5 S-ECO mode parameters 3
Parameter
Working mode
Harmonic
compensation
Harmonic
compensation output
current THD
threshold
Issue 02 (2024-01-05)
Description
Specifies the UPS working
mode.
NOTE
The following describes how to set
S-ECO or ECO mode:
● If both the power module and
bypass module support S-ECO
mode, the working mode can
be set to S-ECO, and the ECO
option is unavailable.
● If the modules do not support
S-ECO mode, the working
mode can be set to ECO, and
the S-ECO is unavailable.
● If the system runs in S-ECO
mode but the hardware is
changed and does not support
it, the system displays the
message "The current hardware
does not support S-ECO. The
system will work in ECO mode."
After you click OK, the system
transfers to the ECO mode (5
ms interruption may occur
during the transfer to the ECO
mode).
When Working mode is set to
S-ECO, you can enable or
disable harmonic compensation.
When Working mode is set to
S-ECO and Harmonic
compensation is set to Enable,
set Harmonic compensation
output current THD threshold
as required.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Single UPS Commissioning
Default Value
Normal mode
Enable
> 5%
Value Range
Normal mode,
ECO/S-ECO, Self-
load mode,
Converter mode
Disable, Enable
>5%, > 10%, >
20%, > 30%
78