ICM and ICMTS Motorized Valves with ICAD Actuators
Parameter
Description and selection
Label ID
name
options
Readout the internal tem-
perature measured on the
ICAD motor board in degree
Temperature
celcius. -500...1400 points,
ID42
where 10 = 1°C (I.e. -125 =
-12.5°C;
1245 = 124.5°C)
Manage if ICAD broadcasts
Bluetooth for remote con-
Bluetooth
ID54
nection via APP.
1: enable; 0: disable
Enable/disable Modbus to
manage if data can be read
Modbus
ID237
and set via Modbus connec-
tion. 1 = enable; 0 = disable

Alarms/Alarm Parameters

Parameter
Description and selection
Label ID
name
options
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
A1
[ID48 (while the device is
timestamp
working)] - [event/alarm
ID120
(Warn: Valve
timestamp (point in ID48 at
no con g)
which the current event oc-
curred)] = minutes that have
passed since the event/
alarm occurred (to show XX
minutes(or hours) ago)
A2(1)
Timestamp of the alarm oc-
timestamp
currence relative to the run-
(Alarm: IO
time counter (ID48),
ID121
MCU comm
Or -1 (0xFFFFFFFF in hex) if
fail)
the alarm is not set
A2(2)
Timestamp of the alarm oc-
timestamp
currence relative to the run-
(Alarm: Motor
time counter (ID48),
ID122
open-load
Or -1 (0xFFFFFFFF in hex) if
status)
the alarm is not set
Timestamp of the alarm oc-
A3(1)
currence relative to the run-
timestamp
time counter (ID48),
ID123
(Alarm: AI er-
Or -1 (0xFFFFFFFF in hex) if
ror: > 22 mA)
the alarm is not set
Timestamp of the alarm oc-
A3(2)
currence relative to the run-
timestamp
time counter (ID48),
ID124
(Alarm: AI er-
Or -1 (0xFFFFFFFF in hex) if
ror: < 2 mA)
the alarm is not set
Timestamp of the alarm oc-
A3(3)
currence relative to the run-
timestamp
time counter (ID48),
ID125
(Alarm: AI er-
Or -1 (0xFFFFFFFF in hex) if
ror: > 12 V)
the alarm is not set
Timestamp of the alarm oc-
A3(4)
currence relative to the run-
timestamp
time counter (ID48),
ID126
(Alarm: AI er-
Or -1 (0xFFFFFFFF in hex) if
ror: < 1 V)
the alarm is not set
© Danfoss | Climate Solutions | 2024.01
Factory set‐
Min.
Max.
ting
-500
1400
0
0
1
1
0
1
1
Factory set‐
Min.
Max.
ting
4294967295
(-1,
-1
4294967294
or
0xFFFFFFFF
in hex)
4294967295
(-1,
-1
4294967294
or
0xFFFFFFFF
in hex)
4294967295
(-1,
-1
4294967294
or
0xFFFFFFFF
in hex)
4294967295
(-1,
-1
4294967294
or
0xFFFFFFFF
in hex)
4294967295
(-1,
-1
4294967294
or
0xFFFFFFFF
in hex)
4294967295
(-1,
-1
4294967294
or
0xFFFFFFFF
in hex)
4294967295
(-1,
-1
4294967294
or
0xFFFFFFFF
in hex)
Pass‐
Alterna‐
word
Modbus
tive
Size in
level to
address
Modbus
bytes
Read -
address
Write
3050
3334
2
1
3076
3361
1
1 - 2
3104
3395
1
1 - 2
Pass‐
Alterna‐
word
Modbus
tive
Size in
level to
address
Modbus
bytes
Read -
address
Write
3200 ...
3404 ...
4
1
3201
3405
3202 ...
3406 ...
4
1
3203
3407
3204 ...
3408 ...
4
1
3205
3409
3206 ...
3410 ...
4
1
3207
3411
3208 ...
3412 ...
4
1
3209
3413
3210 ...
3414 ...
4
1
3211
3415
3212 ...
3416 ...
4
1
3213
3417
BC465027827472en-000102 | 31
Read
only
(RO) /
Persis‐
Modbus
Read
tent
func‐
Write
Yes/No
tion
(RW) /
Write
(W)
RO
No
3
RW
Yes
3 & 6, 16
RW
Yes
3 & 6, 16
Read
only
(RO) /
Persis‐
Modbus
Read
tent
func‐
Write
Yes/No
tion
(RW) /
Write
(W)
RO
No
3
RO
No
3
RO
No
3
RO
No
3
RO
No
3
RO
No
3
RO
No
3