ICM and ICMTS Motorized Valves with ICAD Actuators

Analog Output

Table 7: Current
Output range
Load
Output error
Recommended external resistor for Hot application

Digital Input

Digital ON/OFF input by means of voltfree contact (Signal/Telecom relays with gold-plated contacts recommended)
– Voltage input used.
Table 8: Current
Rth rise(OFF)
Rth fall(ON)

Digital Output

Digital Output - 3 pcs. NPN transistor output.
External supply
7 – 24 V DC (same supply as for ICAD can be used, but please note that the galvanically isolated system will then be
spoiled).
On resistance
55 Ω + diode voltage 0.7 V DC
Max 70 Ω at 50 mA
Max Output current: 50 mA
Reverse polarity protection: Yes
Overcurrent protection: No

Wiring the ICAD actuator

There are three cables which are connected to the ICAD motor with M12 connectors:
Figure 6: Cable Connectors
Data communication
© Danfoss | Climate Solutions | 2024.01
Power supply
III
Control signals
0/4 – 20mA
<800 Ω
<±1.5% of the full scale
Rext=800 Ω-load 1W power rate
>10 kΩ
< 45 Ω
II
C C
I
D D
E E
F F
2
B B
A A
3
G G
4
BC465027827472en-000102 | 10
1