Status/I/O Status - Danfoss ICM User Manual

Motorized valves with actuators
Table of Contents

Advertisement

ICM and ICMTS Motorized Valves with ICAD Actuators
Parameter
Description and selection
Label ID
name
options
Enable/disable Modbus to
Modbus
manage if data can be read
ID237
enable
and set via Modbus connec-
tion. 1: enable; 0: disable
Modbus
Active when ID2 is modulat-
ID155
heartbeat
ing and ID3 is modbus
enable
1: enable; 0: disable
When ID155 Modbus heart-
beat is enabled.
The interval with which the
PLC should send Modbus re-
Modbus
quests to ICAD.
ID156
heartbeat
If the ICAD does not receive
interval
any (read/write parameter)
Modbus request during this
interval, the A3 Alarm (signal
lost) will be set 5...120 sec-
onds (min step – 1)

Status/I/O Status

Parameter
Description and selection
Label ID
name
options
Readout the digital input
when the operation mode
(ID2) is set to ON/OFF or 3-
point control.
3: DI1 - on, DI2 - on;
2: DI1 - o , DI2 - on;
DI
ID37
1: DI1- on, DI2 - o ;
0: DI1- o , DI2 - o ; Note
that for ON/OFF only DI1 is
active:
1: DI1 - on
0: DI1 - o
DO Fully closed status (ON
when OD < 3%)
DO (fully
ID38
close)
1: Yes;
0: No
DO Fully opened status (ON
DO (fully
when OD > 97%)
ID39
open)
1: Yes;
0: No
DO common alarm status
(Active when there are ac-
DO (alarm
tive alarms)
ID40
show)
1: Active;
0: OFF
© Danfoss | Climate Solutions | 2024.01
Factory set‐
Min.
Max.
ting
0
1
1
0
1
0
5
120
30
Factory set‐
Min.
Max.
ting
0
3
0
0
1
0
0
1
0
0
1
0
Pass‐
Alterna‐
word
Modbus
tive
Size in
level to
address
Modbus
bytes
Read -
address
Write
3104
3395
1
1 - 2
3093
3378
2
1 - 2
3094
3379
2
1 - 2
Pass‐
Alterna‐
word
Modbus
tive
Size in
level to
address
Modbus
bytes
Read -
address
Write
3044
3328
1
1
3045
3329
1
1
3046
3330
1
1
3047
3331
1
1
BC465027827472en-000102 | 27
Read
only
(RO) /
Persis‐
Modbus
Read
tent
func‐
Write
Yes/No
tion
(RW) /
Write
(W)
RW
Yes
3 & 6, 16
RW
Yes
3 & 6, 16
RW
Yes
3 & 6, 16
Read
only
(RO) /
Persis‐
Modbus
Read
tent
func‐
Write
Yes/No
tion
(RW) /
Write
(W)
RO
No
3
RO
No
3
RO
No
3
RO
No
3

Advertisement

Table of Contents
loading

Table of Contents