ICM and ICMTS Motorized Valves with ICAD Actuators

Info

Parameter
Description and selection
Label ID
name
options
Name assigned to ICAD as
the identi cation shown on
built-in display and for con-
ICAD name
nection via Bluetooth. 16
ID53
ASCII symbols, 8bits per
symbol
(2 symbols per register)
Readout the ICAD model
type.
3: ICADB TS
ICAD model
ID253
2: ICAD 1200B;
1: ICAD 600B;
0: not con gured;
Readout the valve con gura-
tion for ICAD
12: ICADBTS ICMTS 50/80;
11: ICADBTS ICMTS20;
10: Pilot Valve CVE;
9: ICAD1200B ICM150;
8: ICAD1200B ICM125;
Valve
7: ICAD1200B ICM100;
ID8
con guration
6: ICAD1200B ICM65;
5: ICAD1200B ICM50;
4: ICAD1200B ICM40;
3: ICAD600B ICM32;
2: ICAD600B ICM25;
1: ICAD600B ICM20;
0: not con gured
SW Version
Readout the sofware version
ID221
(High)
of ICAD nn.xx
SW Version
Readout the sofware version
ID222
(Low)
of ICAD xx.nn
Format MM.CC (1 byte Motor
PCB, 1 byte Connector PCB)
Hardware
(e.g. value 0x0102 = 01.02v -
ID143
version
> 01 Motor PCB version, 02
Connector PCB version)
(reserved up to 0xFFFFFFFF)
Indicates if this ICAD has
previously been con gured.
This controls when the setup
Previously
wizard is shown when con-
ID102
con gured
necting to ICAD via the APP.
1: con gured;
0: not con gured
The unique serial number of
ICAD. Number generated by:
nnnnnnnCCCCCCCCPPWWYY
- running number (n) +
Product number (Cs) + Mfg
place& time nnnnnnn part -
Serial
2 registers
ID235
number
CCCCCCCC PP parts - 5 regis-
ters, in ASCII symbols, 8bits
per symbol
(2 symbols per register)
WW part - 1 register
YY part - 1 register
D part - 1 register
Readout the run time in full
hours for the ICAD from
Run time
when it was rst powered on
ID48
or factory reset. Saved every
30min (in minutes)
© Danfoss | Climate Solutions | 2024.01
Factory set‐
Min.
Max.
ting
ICAD
3068 ... 3075
0
3
0
0
13
0
0
255
0
0
255
0
0x0000
0xFFFF
0x0000
0
1
0
0
0
4294967293
0
Pass‐
Alterna‐
word
Modbus
tive
Size in
level to
address
Modbus
bytes
Read -
address
Write
3353 ...
30
1 - 2
RW
3360
3057
3339
1
1
3056
3338
1
1
3048
3332
1
1
3049
3333
1
1
3156 ...
3345 ...
4
1
3157
3346
3089
1
2 - 2
3077 ...
3362 ...
30
1
3086
3371
3060 ...
3347 ...
4
1
3061
3348
BC465027827472en-000102 | 35
Read
only
(RO) /
Persis‐
Modbus
Read
tent
func‐
Write
Yes/No
tion
(RW) /
Write
(W)
3 & 6,
Yes
16
RO
Yes
3
RO
No
3
RO
No
3
RO
No
3
RO
No
3
RW
Yes
3 & 6, 16
RO
Yes
3
RO
Yes
3 & 6, 16

Advertisement