. To prevent damage to O-rings and the valve seat, remove the one-piece ICM bonnet and function module from the valve body prior to welding the valve body in the line. For ICM 0 (3/4” size) the valve seat is not integrated with the valve bonnet and must be separately removed from the valve body with a 1 mm hex key prior to welding (see diagrams below).
Page 4
5. Install the bonnet/function module into the valve body. a. For ICM 0, make sure that the removable orifice seat is installed in the valve body with the small O-ring between the orifice seat and body. Make sure the bonnet gasket is installed and in good condition.
White: common alarm (digital NPN transistor output when combined with yellow wire) • Brown: indicates ICM is fully open (digital NPN transistor output when combined with yellow wire) • Green: indicates ICM is fully closed (digital NPN transistor output when combined...
Page 6
(+ 4-20 mA) Gray Blue (+ 4-20 mA) Optional position feedback Only possible with EKC 347 Optional UPS/battery back up White 24 V d.c Brown Power Green Supply CUSTOMER SUPPLIED DKRCI.EI.HT0.A1. / 50H1639 Danfoss (USCO / MKS), 11- 006...
Page 7
K1 : Common Alarm K2 : ICM fully open Optional UPS/ White K3 : ICM fully closed battery back up Brown Green 24 V d.c Power Supply CUSTOMER SUPPLIED DKRCI.EI.HT0.A1. / 50H1639 Danfoss (USCO / MKS), 11 - 006...
4. Repeat this procedure for all parameters. 5. Exit from the parameter list by pressing and holding the middle button for seconds. The ICAD will automatically exit if no buttons are pushed for 0 seconds. DKRCI.EI.HT0.A1. / 50H1639 Danfoss (USCO / MKS), 11- 006...
When the ICM ¡26 valve size is selected, the ICAD will calibrate itself to the ICM valve and will then be ready for control by a 4-0mA signal. For most applications, this is the only programming that will need to be done if the ICAD is going to be controlled by a 4-0mA input.
Installation, Programming, and Troubleshooting Troubleshooting The manual tool should always be ordered with any ICM/ICAD assembly. This tool gives the user the ability to remove the ICAD actuator and manually rotate the valve in the open or The Manual Tool close direction depending on need and application.
If supply voltage < 18 V d.c. Troubleshooting Tips Problem Possible cause and solution The valve is not working and an A1 is The ICM valve size was not selected in flashing in the display. parameter . See the programming ¡26 section on page 9.
UPS mode. • Add a solenoid valve in front of the ICM. This is a very simple solution provided that there is no issue associated with the additional pressure drop through the solenoid valve.