ICM and ICMTS Motorized Valves with ICAD Actuators

Service/System Parameters

Parameter
Description and selection
Label ID
name
options
Use a service reminder for
when the valve should be
serviced in order to maintain
operation of the system.
Service
ICAD will initiate a warning
ID49
when Time to next service
reminder
(ID50) reaches 0. Valves
should be checked once a
year. This is enabled by de-
fault. 1: ON; 0: OFF
Use a service reminder for
when the valve should be
serviced in order to maintain
operation of the system.
Reset service
ICAD will initiate a warning
ID51
interval
when Time to next service
(ID50) reaches 0. Valves
should be checked once a
year. This is enabled by de-
fault. 1: ON; 0: OFF
Indicates the service interval
Service
until the valve should be
ID234
interval
checked. This is by default
once a year. 1...999 (in days)
Clear event log
1: Yes: All event log entries
will be hidden. The parame-
Clear event
ter will automatically be set
ID26
log
back to 'no' when hide has
nished
0: No: Not active
The time user remains log-
ged in to service mode with-
User logout
out doing any actions before
ID52
time
automatically logged out
30...1200 (in seconds)
Name assigned to ICAD as
the identi cation shown on
built-in display and for con-
ID53
ICAD name
nection via Bluetooth. 16
ASCII symbols, 8bits per
symbol
(2 symbols per register)
Enable ICAD to broadcast
Bluetooth
Bluetooth for remote con-
ID54
enable
nection via APP.
1: enable; 0: disable
Factory reset action for
ICAD
1: Yes: All parameters will be
returned to factory default
settings, and the event log
Factory reset
ID236
will be cleared. The parame-
ter will automatically be set
back to 'no' when factory re-
set has nished
0: No: Not active
© Danfoss | Climate Solutions | 2024.01
Factory set‐
Min.
Max.
ting
0
1
0
0
1
0
1
999
365
0
1
0
30
1200
360
ICAD
0
1
1
0
1
0
Pass‐
Alterna‐
word
Modbus
tive
Size in
level to
address
Modbus
bytes
Read -
address
Write
3062
3349
1
1 - 2
3066
1
2 - 2
3065
3352
2
1 - 2
3123
1
2 - 2
3067
2
2 - 2
3068 ...
3353 ...
30
1 - 2
3075
3360
3076
3361
1
1 - 2
3087
1
2 - 2
BC465027827472en-000102 | 25
Read
only
(RO) /
Persis‐
Modbus
Read
tent
func‐
Write
Yes/No
tion
(RW) /
Write
(W)
RW
Yes
3 & 6, 16
RW
No
3 & 6, 16
RW
Yes
3 & 6, 16
RW
No
3
RW
Yes
3 & 6, 16
RW
Yes
3 & 6, 16
RW
Yes
3 & 6, 16
RW
No
3 & 6, 16