Service/Advanced Control Parameters - Danfoss ICM User Manual

Motorized valves with actuators
Table of Contents

Advertisement

ICM and ICMTS Motorized Valves with ICAD Actuators
Parameter
Description and selection
Label ID
name
options
Set the desired opening
Requested
degree Only when main
Opening
ID4
switch is set to manual
Degree (set-
(ID1=1) 0...100% (min step
point)
– 1%)
The opening degree re‐
quested through Modbus
Only active when Main
Requested
switch is set to auto (ID1=0)
Opening
and input signal is set to
ID203
Degree (set-
Modbus (ID3=4). 0...10000
point)
points, where 100 = 1%
(i.e. 5021 = 50.21%; 10000 =
100.00%)
Change password for level
2 acess.
Service
Level 2 will give acess to
passcode
read/write parameters of
ID24
(Level 2)
level 2. See Column "Pass-
word level to Read - Write"
and "Read only / Read Write"

Service/Advanced Control Parameters

Parameter
Description and selection
Label ID
name
options
Opening speed Only active
when Operation mode (ID2)
Speed
is set to 3-point.
ID5
positive, 3-
Percentage of full
point
speed.1...100% (min step –
1%)
Closing speed Only active
when Operation mode (ID2)
Speed
is set to 3-point.
ID75
negative, 3-
Percentage of full
point
speed.1...100% (min step –
1%)
Opening speed Only active
Speed
when Operation mode (ID2)
positive,
ID6
is set to ON/OFF.
on/o
Percentage of full speed
1...100% (min step – 1%)
Closing speed Only active
Speed
when Operation mode (ID2)
negative,
is set to ON/OFF.
ID76
on/o
Percentage of full speed
1...100% (min step – 1%)
Speed while modulating
Only active when Operation
mode (ID2) is set to Modu-
Speed,
lating.
ID7
modulating
Percentage of full speed
1...100% (min step – 1%)
For CVE valve max value =
50%
© Danfoss | Climate Solutions | 2024.01
Factory set‐
Min.
Max.
ting
1
100
0
0
10000
0
0
99999999
12131400
Factory set‐
Min.
Max.
ting
1
100
10
1
100
10
100 - ICAD
1
100
600; 50 -
ICAD 1200
100 - ICAD
1
100
600; 50 -
ICAD 1200
100 - ICAD
1
100
600; 50 -
ICAD 1200
Pass‐
Alterna‐
word
Modbus
tive
Size in
level to
address
Modbus
bytes
Read -
address
Write
3003
3303
1
1 - 1
3004
3304
2
1 - 1
3005 ...
4
2
3006
Pass‐
Alterna‐
word
Modbus
tive
Size in
level to
address
Modbus
bytes
Read -
address
Write
3011
1
2 - 2
3012
1
2 - 2
3013
1
2 - 2
3014
1
2 - 2
3015
1
2 - 2
BC465027827472en-000102 | 19
Read
only
(RO) /
Persis‐
Modbus
Read
tent
func‐
Write
Yes/No
tion
(RW) /
Write
(W)
RW
No
3 & 6, 16
RW
No
3 & 6, 16
W
Yes
16
Read
only
(RO) /
Persis‐
Modbus
Read
tent
func‐
Write
Yes/No
tion
(RW) /
Write
(W)
RW
Yes
3 & 6, 16
RW
Yes
3 & 6, 16
RW
Yes
3 & 6, 16
RW
Yes
3 & 6, 16
RW
Yes
3 & 6, 16