Wiring Diagram Showing Icad Wired To A Plc Or Other Type Of Third Party Electronics - Danfoss ICM User Manual

Motorized valves with actuators
Table of Contents

Advertisement

ICM and ICMTS Motorized Valves with ICAD Actuators
Figure 7: ICAD back Description
ICAD back
Ref
Color
A
Black
B
Brown
C
B
C
Red
D
A
E
G
D
Orange
E
Yellow
F
F
Green
G
Blue
II
I
Black
II
White
III
I
III
Brown
IIII
Blue
2
1
White/Blue
2
White/Orange
1
3
3
Blue
4
Orange
4
*Uniterruptable Power Supply
**The ICAD is a class III appliance

Wiring diagram showing ICAD wired to a PLC or other type of third party electronics

Figure 8: ICAD wired to a PLC
1
Control
2
Power supply cable
3
Data cable
 NOTE:
Note: The ICAD supplies the power for the 4–20 mA feedback signal.
© Danfoss | Climate Solutions | 2024.01
Description
-
Common alarm
-
ICM fully open
-
ICM fully closed
-
GND ground
+
0/4 –20 mA Input
+
0/2 – 10 V input or digital input for o
+
0/4 – 20 mA Output
+
Fail safe supply. Battery / UPS* 19 V DC
+
Supply voltage
24 V DC 2A, or more, per ICAD recommended
-
ICAD PSU must be SELV**, >15 W
UPS Signal of Health - optional depending on ID31:
+
'UPS supply' set to 'Yes'
RS485/ Ethernet
(-) / TX+
GND / RX+
(+) / TX-
GND / RX-
Terminal box
1
2
2
3
3
cable
Data – (B) / Transmit Pair(+)
Ground / Receiving Pair(+)
Data + (A) / Transmit Pair(-)
Ground / Receiving Pair(-)
+
-
Yellow
Orange
+
Blue
Blue
Black
White
Brown
BC465027827472en-000102 | 11
Digital
output
control
PLC
Active 4–20 mA PLC output to control ICAD
Active 4–
mA PLC output to control ICAD
-
Passive 4 –20 mA PLC input
for valve position feedback
Passive 4–20 mA PLC input
for valve position feedback
+
Optional UPS Signal of Health
+
Optional UPS/battery back up
+
24 V DC
Power
-
Supply
CUSTOMER SUPPLIED

Advertisement

Table of Contents
loading