5 How to Control
Bit 06, Ramp stop/start:
Bit 06 = '0' causes a stop, in which the motor speed is ramped down to
stop via the selected
ramp down
quency converter to start the motor, if the other starting conditions have
been fulfilled.
NB!
In par. 8-53
to define how Bit 06 Ramp stop/start gates with the
corresponding function on a digital input.
Bit 07, Reset:
Bit 07 = '0' no reset. Bit 07 = '1' resets a trip. Reset is activated on the
5
leading edge of the signal, i.e. when changing from logic '0' to logic '1'.
Bit 08, Jog:
Bit 08 = '1' causes the output frequency to be determined by
par. 3-19
Jog Speed [RPM]
Bit 09, Selection of ramp 1/2:
Bit 09 = '0' means that ramp 1 is active (par. 3-40
par. 3-47
Ramp 1 S-ramp Ratio at Decel. Start
Ramp 2 Type
ramp 2 (par. 3-50
Decel. Start
) is active.
Bit 10, Data not valid/Data valid:
This bit tells the frequency converter whether the control word is to be
used or ignored. Bit 10 = '0' causes the control word to be ignored, Bit
10 = '1' causes the control word to be used. The control word is always
contained in the telegram, regardless of which type of telegram is used,
so this function is useful for 'turning off' the control word when not re-
quired for updating or reading parameters.

5.2.2 Status Word according to FC ProfileDrive Profile (STW)

Illustration 5.2: (par.8-10
26
parameter. Bit 06 = '1' permits the fre-
Start Select
Start select a selection is made
.
Ramp 1 Type
). Bit 09 = '1' means that
Ramp 2 S-ramp Ratio at
to par. 3-57
Control Word Profile
)
MG.90.J2.02 - VLT
Bit 11, Relay 01:
Bit 11 = '0' Relay not activated. Bit 11 = '1' Relay 01 activated, provided
Control word bit 11
has been chosen in par. 5-40
Bit 12, Relay 02:
Bit 12 = '0' Relay 02 has not been activated. Bit 12 = '1' Relay 02 has
been activated, provided
par. 5-40
Function Relay
.
Bit 13/14, Selection of set-up:
Bits 13 and 14 are used to select one of four menu set-ups according to
the following table:
Set-up
1
2
3
4
The function is only possible when
Active Set-up
to
par. 0-10
.
NB!
In par. 8-55
how Bit 13/14 gates with the corresponding function
on the digital inputs.
Bit 15 Reverse:
Bit 15 = '0' causes no reversing. Bit 15 = '1' causes reversing. Note: In
the factory setting reversing is set to
lect
. Bit 15 causes reversing only when
Logic OR
or
is selected.
Bit
Bit value = 0
00
Control not ready
01
Drive not ready
02
Coasting
03
No error
04
No error
05
Reserved
06
No error
07
No warning
08
Speed ≠ reference
09
Local operation
10
Out of frequency limit
11
No operation
12
Drive ok
13
Voltage ok
14
Torque ok
15
Thermal ok
®
is a registered Danfoss trademark
MCA 121 EtherNet/IP
Function Relay
Control word bit 12
has been chosen in
Bit 14
Bit 13
0
0
0
1
1
0
1
1
Multi-Set-ups
is selected in
Set-up Select
a selection is made to define
digital
in par.8-54
Reversing Se-
Ser. communication
Logic AND
,
Bit value = 1
Control ready
Drive ready
Enable
Trip
Error (no trip)
-
Trip lock
Warning
Speed = reference
Bus control
Frequency limit ok
In operation
Stopped, auto start
Voltage exceeded
Torque exceeded
Thermal exceeded
.