Step 2. Program The Led; Simultaneous Alarm Display; Creating Annunciation Zone Lists - Simplex 4010ES IDNAC Installation Manual

Fire alarm system
Hide thumbs Also See for 4010ES IDNAC:
Table of Contents

Advertisement

10.1.2

Step 2. Program the LED

1.
Select one of the multicolor LEDs (0-5-11, 0-5-12, or 0-5-13) to program (Figure 57).
2.
Click on the Point Type list box and select LEDYELLOW.
3.
Click on the Mode drop-down list box and select ON.
Enter A112 (no spaces) in the Reference Address field.
4.
10.2

Simultaneous alarm display

ULC requires that every fire panel be capable of indicating the presence of up to eight simultaneous alarms. The 48-LED Module supplied
with some configurations of the 4010ES panels is used for that purpose. Implementing this on the 4010ES is a two-step process, as
follows:
1.
Create Annunciation Zone Lists. Divide the panel's initiating devices into physical areas (by floor, by department, etc.). Create a
user-defined list for each zone and include all of the initiating devices for the zone in the list. See "Creating Annunciation Zone
Lists" below for information on doing this.
Note: Annunciation Zone Lists are only necessary if you are using addressable devices. If you are using hardwired monitor
zones, it is not necessary to create a list.
2.
Program LED modes and reference addresses. This step associates the address of the zone list with the LED and its mode.
10.2.1

Creating annunciation zone lists

To create the annunciation zone lists – which are the lists containing the initiating devices for each zone – follow these steps.
1.
Click on the List tab in the main ES Panel Programmer window.
Right-click anywhere in the TagList dialog. A menu appears, containing a range of options. Select Add List. A tag list, similar to
2.
the following, appears.
page 69
4010ES IDNAC Fire Alarm System Installation Guide
Figure 57: The Display tab: LEDs
579-1150 Rev M