Note: The 2098-9739 Relay is used as an example. Other UL Listed 24VDC EOL relays can be used, depending on the application.
6.3

Connecting 4010ES basic components

6.3.1

Connecting the CPU and the operator interface

Note:
All the basic components come pre-installed with the system. The connections are shown for reference purposes.
To connect the CPU and the operator interface, follow the steps below:
1.
Place the white spacer on the dead front.
2.
Attach the CPU card and the piezo to the dead front, using metal screws provided.
Attach the Keypad Membrane cable of the operator interface to port P8 on the CPU card (Figure 29). To do so:
3.
a.
Slide down the keypad connector shroud on the CPU card.
b.
Insert the Keypad Membrane cable into the connector. Do not twist the flat cable.
c.
Slide the shroud back up into the connector while holding the flat cable in place.
4.
Attach the Ethernet connection board using the 734-232 RJ45 cable.
5.
Attach the Perle box using the 734-229 cable.
Connect port P9 or P10 of the CPU card to the dead front connection (P1) port on the top-bay power distribution interface
6.
(PDI) card (Figure 29 and Figure 30). Use the 734-008 4-pin connector harness provided.
page 40
Figure 28: The EOL relay
4010ES IDNAC Fire Alarm System Installation Guide
579-1150 Rev M