3.3.1

ESS LEDs

The ESS card is equipped with LEDs that help the user diagnose the card and system troubles.
LED number
Identification
LED1
IDNet negative earth
LED2
IDNet positive earth
LED3
IDNet trouble
LED4
IDNet 4100 communications
LED5
IDNet loop A
LED6
IDNet loop B
LED7
IDNAC 1 fault
LED8
IDNAC 2 fault
LED9
AC power
LED10
Communication loss
LED11
E
LED12
D
LED13
C
LED14
B
LED15
A
*The IDNet circuit on the ESS is electrically isolated and has its own earth fault detection circuit. The IDNet earth fault detection circuit
detects a 10 KOhms (or less) stray impedance to earth ground.
The ESS system trouble LED codes are indicated by LEDs A to E.
A
B
C
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
ON
page 17
Table 11: ESS LED identification and definition
Status
On = IDNet negative terminal is connected to earth.*
On = IDNet positive terminal is connected to earth.*
Steady = No devices are detected.
Blink = Short circuit trouble.
On = Communication loss.
On = Class A/Open trouble.
On = Class B/Open trouble.
On = There is a fault on IDNAC SLC 1 circuit.
On = There is a fault on IDNAC SLC 2 circuit.
On = ESS is connected to the main AC power.
On = Communication with the FACU is lost.
These 5 LEDs are used to signal various trouble conditions on the ESS and
its SLC.
See Table 12 for the LED system codes.
Table 12: System trouble LED codes
D
E
Description:
OFF
OFF
No Trouble: There are no troubles detected on the system.
OFF
OFF
AC Fail: The AC power is disconnected but the battery is working.
OFF
OFF
Low Battery: The battery charge is under 22V.
Battery Cutout: The battery charge is below 20V. At this point if jumper P19 is set
OFF
OFF
to "battery disconnect when depleted" the system will shut down.
Depleted/Missing Battery: If jumper P19 is not set to "battery disconnect
when depleted" this trouble will appear when the battery charge is below 20V.
OFF
OFF
This code will also appear if the system cannot detect the battery.
OFF
OFF
Charger Trouble: There is a trouble with the battery charger.
Card Overcurrent: The ESS module or another system card is drawing too much
OFF
OFF
current.
OFF
OFF
Negative Earth: The circuit is shorted to ground on the negative wire.
ON
OFF
Positive Earth: The circuit is shorted to ground on the positive wire.
City Circuit 1 Trouble: The trouble configured on the City Card's circuit one has
ON
OFF
been triggered.
City Circuit 2 Trouble: The trouble configured on the City Card's circuit two has
ON
OFF
been triggered.
AuxNAC Open: Depending on the chosen configuration, either the Aux circuit or
ON
OFF
the NAC circuit is open.
AuxNAC Short: Depending on the chosen configuration, either the Aux circuit or
ON
OFF
the NAC circuit is experiencing a short circuit.
AuxNAC Overcurrent: Depending on the chosen configuration, either the Aux
ON
OFF
circuit or the NAC circuit is drawing too much current.
OFF
ON
Unassigned.
ON
ON
Unassigned.
4010ES IDNAC Fire Alarm System Installation Guide
579-1150 Rev M