Simplex 4010ES IDNAC Installation Manual page 48

Fire alarm system
Hide thumbs Also See for 4010ES IDNAC:
Table of Contents

Advertisement

Note:
1.
Wire size must be between 18 AWG (0.8231 mm
2.
Maximum wiring distance: 2,500 feet (762 m) to device from CPU card.
3.
Maximum "T" tapping length: 10,000 feet (3,048 m).
4.
Maintain correct polarity on terminal connections. Do not loop wires under terminals.
5.
If Class A is not used, leave loop back wires from A+ to B+ and A- to B- on RUI terminal blocks.
6.
Shield wire is not required. Twisted wire is recommended for improved noise immunity.
7.
Internal harness part numbers: 0734-241 (1 bay), 0734-243 (2 bay).
For more detailed field wiring information on each device, refer to its specific installation instructions manual. See
devices, for a list of instructions manuals.
page 46
Figure 34: RUI wiring to the host panel
2
) and 12 AWG (3.309 mm
4010ES IDNAC Fire Alarm System Installation Guide
2
).
Available panels and
579-1150 Rev M