4010ES IDNAC Fire Alarm System Installation Guide
Figure 38: Grounding wire
Figure 39: AC block labels for AC power connections
Note:
In 220-240 V panels, the 4010ES requires a true transformer output of 220-240 V. Do not connect two out of phase "hot" wires to create
the desired voltage.
When connecting the AC power wire to the AC block, it needs to pass through a ferrite bead to reduce radiated emissions. Route the black
and white AC power wires to the supplied ferrite bead. Loop the wires twice through the bead and secure with two cable ties as shown in
Figure 40. The cable ties are supplied in the ship group that comes with the panel.
Figure 40: AC Power line ferrite bead
page 50
579-1150 Rev M