Voltage
24V special application
rating
Rating
2 A, maximum.
18 AWG (min.)
Wiring
gauge
to 12 AWG (max.).
Wiring Notes:
1. All wiring from the AUX/NAC is power limited.
2. Conductors must test free of all grounds and stray voltages before connection to appliances and panel.
3. Terminate Class B NACs as shown using 733- 894. For Canadian applications, mount end-of-line resistor to Simplex-US Model 431537
EOL plate in accordance with ULC-S527.
4. If circuit is terminated with a 10k EOLR, at the terminals, remove this resistor before wiring.
5. If wiring is routed outside the building, use of a listed secondary protector is required. Use Simplex 2081- 9028 or 2081-9044. A
protector must be installed at each building exit/entrance. Each 2081-9028 adds 0.2 ohms wiring resistance. 2081-9044 adds 6 ohms
wiring resistance, and will greatly reduce wiring distance.
6. External wiring from the auxiliary power tap (AUX) is not supervised unless an end-of-line relay is wired to auxiliary power, and
normally open contacts are monitored by the FACU (IDNet device or IO point). Relay current must be considered as part of the load.
When only addressable devices are connected to the auxiliary power tap, an end-of-line relay is not required because the power for
the addressable devices is supervised due to the device being addressable. The preceding configurations provide AUX Power Class B.
7. Install a ferrite bead close to the AUX field wiring terminals for FCC compliance, as shown in Figure 48. Order separately as needed
(order kit 4100-5129).
Alarm current
20 AWG
0.25
617 ft
0.50
308 ft
0.75
206 ft
1.00
154 ft
1.25
123 ft
1.50
103 ft
1.75
88 ft
2.00
77 ft
Note:
This chart indicates the maximum distance for 1/4 -2A loads. Wiring distance is from the panel terminals to the last appliance. Use of a
2081-9044 protector reduces wiring distance.
page 59
Table 32: AUX/NAC wiring specification
Table 33: NAC wiring limits
18 AWG
16 AWG
14 AWG
981 ft
1560 ft
2480 ft
490 ft
780 ft
1240 ft
327 ft
520 ft
827 ft
245 ft
390 ft
620 ft
196 ft
312 ft
496 ft
163 ft
260 ft
413 ft
140 ft
223 ft
354 ft
123 ft
195 ft
310 ft
4010ES IDNAC Fire Alarm System Installation Guide
Figure 48: Simple NAC wiring
12 AWG
Line resistance (Ohms)
3944 ft
14.00
1972 ft
7.00
1315 ft
4.67
986 ft
3.50
789 ft
2.80
657 ft
2.33
563 ft
2.00
493 ft
1.75
579-1150 Rev M