Simplex 4010ES IDNAC Installation Manual page 22

Fire alarm system
Hide thumbs Also See for 4010ES IDNAC:
Table of Contents

Advertisement

Standby conditions*
Total current for fully loaded IDNAC and IDNet channels (254 and 250 devices respectively) in
standby
*Additional standby conditions: Auxillary relay activated, power trouble LED on, battery charger off, auxiliary power load = 0 mA.
Alarm conditions**
Alarm, IDNet LED ON, no IDNet devices connected
Add to base for each additional set of 50 IDNet devices in alarm
Total current for a fully loaded IDNet channel in alarm (20 LEDs on)
**Additional alarm conditions: Auxillary relay activated, power trouble LED on, battery charger off, auxiliary power load = 0 mA, IDNAC alarm load
= 0 mA, IDNet = 35 V.
***Notification power must also be taken into account for alarm current. Consult the notification appliance's installation manual to determine the
current draw for each appliance used.
page 20
Table 16: ESS current specifications
4010ES IDNAC Fire Alarm System Installation Guide
Current (battery 24V)
563 mA
Current (battery 24V)
275 mA
50 mA
565 mA***
579-1150 Rev M