Cpu Jumper Settings; Cpu Switches - Simplex 4010ES IDNAC Installation Manual

Fire alarm system
Hide thumbs Also See for 4010ES IDNAC:
Table of Contents

Advertisement

Reference
designator
Silkscreen name
Color
Bootloader
Initialization
Bad Master CRC or
No Master Present
Diagnostic Fail - RAM On
Diagnostic Fail -
Bootloader CRC
Status
Downloading Master On
Downloading CFIG
Downloading MsgLib On
Downloading
Bootloader
Download
Successful
3.1.2

CPU Jumper Settings

Reference designator
P5
P1
P2
Note: Some devices that connect to RUI have inherently grounded shield terminals, in which case, 24C cannot be used. If 24C is used, a
Negative Earth Fault will occur.
3.1.3

CPU Switches

Reference
Silkscreen name
designator
SW1
RESET
SW3
COLD START
page 13
Table 5: Bootloader status LEDs
LED7
LED8
A
B
Green
Green
On (0.25 s)
On (0.25 s)
Off (0.25 s)
Off (0.25 s)
Off
Off
Off
Off
On
On
Off
Off
Off
Off
On
On
On
Table 6: CPU settings
Silkscreen name
BATTERY
RUI CKT
RUI SHIELD
Table 7: Switches
Function
Short press (< 3 seconds) to activate a software-controlled reset (warm start).
Press and hold (> 3 seconds) to force a hardware reset (also a warm start).
Generally, unless the CPU card appears to be locked up, you should always use the
software-controlled reset.
A warm start preserves the logs and the disabled status of any points that are in the
disabled state.
During startup, press and hold this button to clear all history logs and enable any
points that were previously disabled.
4010ES IDNAC Fire Alarm System Installation Guide
LED9
C
Green
On (0.25 s)
Off (0.25 s)
Off
Off
Off
Off
On
On
On
On
Position
Function
1-2
Enable RAM Battery Backup
2-3 (default)
Disable RAM Battery Backup
1-2 (default)
Disable RUI
2-3
Enable RUI
1-2 (default)
RUI shield tied to 24C (Note)
2-3
RUI shield tied to Earth
LED10
D
Green
On (0.25 s)
Off (0.25 s)
On
On
On
On
On
On
On
On