Appliance LED Activation

Procedure

Note:
In order for Diagnostics to operate properly all appliances must
be inactive prior to diagnostic activation.
Use the following procedure to activate all of the TrueAlert Appliance LEDs
assigned to a particular TrueAlert Addressable Controller.
1.
Log on the 4100/4020 at the appropriate Access Level.
2.
On the Operator Interface Panel, go to the TrueAlert appliance function
screen and turn on the appliance LEDs on the TrueAlert Addressable
Controller. Verify that all of the appliance LEDs assigned to the TrueAlert
Addressable Controller turn on. (The 4100/4020 display will remained
locked onto this screen for eight hours or until you turn off the LEDs.)
3.
From the Operator Interface Panel display under the TrueAlert appliance
function screen, turn off the appliance LED's on the TrueAlert
Addressable Controller.
If more than one TrueAlert Addressable Controller is connected to the system
repeat the above procedure on the remaining Addressable Controllers.