PID Instruction (FNC 88)
3.2

Details of Parameters

3.2.1
Sampling time (T
Set the cycle time (ms) for the PID operation.
• In PID control and auto-tuning (Limit cycle method)
Set the sampling time longer than the operation cycle of the PLC.
• In auto-tuning (Step response method)
Set the sampling time to 1,000 ms (= 1 second) or more.
1. Maximum error
The maximum error of the sampling time (T
cycle)."
1) When the sampling time (T
Fluctuation of the maximum error described above may cause a problem.
In such a case, execute the PID instruction in the constant scan mode, or program it in a timer interrupt
routine.
2) When the sampling time (T
A PID operation error (K6740) occurs, however when PID operation is executed, the sampling time (T
equal to the operation cycle of the PLC.
In such a case, use the PID instruction in a timer interrupt (I6 to I8), and clear
executing the PID instruction.
→ For a detailed description, refer to FX
X000
I610
PLC User's Manual - Analog Control Edition
): (S3)
S
S
) is a small value
S
) is shorter than one operation cycle of the PLC
S
FNC 12
K 0
D107
MOVP
FNC 88
D 0
D 1
PID
Setting range: 1 to 32767 [ms]
) is from "-(one operation cycle + 1 ms)" to "+(one operation
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
- Basic & Applied Instruction Edition
S
+7 is reset.
3
(When the interrupt routine is executed for the
first time, the register for internal processing is
cleared by the pulse generation command.)
The PID operation is
D100
D150
executed.