Temperature Sensor Input; Fx -4Ad-Pt-Adp - Mitsubishi Electric MELSEC-FX3S Series Manual

Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
Common Items
4.4

Temperature Sensor Input

4.4.1
FX
-4AD-PT-ADP
3U
Specifications
Number of input points
Input signal
Rated temperature range
Digital output
Resolution
• Ambient temperature: 25°C±5°C ±0.5% for full scale
Overall accuracy
• Ambient temperature: 0°C to 55°C ±1.0% for full scale
• FX
Time required for
conversion
• FX
Input characteristics
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
0 points
occupied
(This number of points is not related to the maximum number of input/output points of the PLC.)
PLC User's Manual - Analog Control Edition
Centigrade (°C)
3-wire platinum resistance thermometer sensor(s)
-50°C to +250°C
-500 to +2500
0.1°C
/FX
Series PLC : 200μs (Data updated every scan time.)
3U
3UC
/FX
/FX
Series PLC : 250μs (Data updated every scan time.)
3S
3G
3GC
+2550
+2500
-50°C
0
+250°C
Temperature
-500
-550
4 Comparison of Performance Specifications
FX
-4AD-PT-ADP
3U
Fahrenheit (°F)
4ch
JIS C 1604-1997
-58°F to +482°F
-580 to +4820
+4910
+4820
-58°F
0
-580 Temperature
-670
4.4 Temperature Sensor Input
0.18°F
+482°F
A-45
A
B
C
D
E
F
G
H
I
J