Fx 3U -4Ad-Ptw-Adp - Mitsubishi Electric MELSEC-FX3S Series Manual

Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
Common Items
4.4.2
FX
-4AD-PTW-ADP
3U
Specifications
Number of input points
Input signal
Rated temperature range
Digital output
Resolution
Overall accuracy
Time required for
conversion
Input characteristics
Insulation method
Number of I/O points
occupied
A-46
PLC User's Manual - Analog Control Edition
3UC
Centigrade (°C)
3-wire platinum resistance thermometer sensor(s)
-100°C to +600°C
-1000 to +6000
0.2°C to 0.3°C
• Ambient temperature: 25°C±5°C ±0.5% for full scale
• Ambient temperature: 0°C to 55°C ±1.0% for full scale
• FX
/FX
Series PLC : 200μs (Data updated every scan time.)
3U
3UC
• FX
/FX
/FX
Series PLC : 250μs (Data updated every scan time.)
3S
3G
3GC
+6150
+6000
-100°C
0
Temperature
-1000
-1150
• The photocoupler is used to insulate the analog input area from the PLC.
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
0 points
(This number of points is not related to the maximum number of input/output points of the PLC.)
FX
-4AD-PTW-ADP
3U
4ch
JIS C 1604-1997
+600°C
4 Comparison of Performance Specifications
4.4 Temperature Sensor Input
Fahrenheit (°F)
-148°F to +1112°F
-1480 to +11120
0.4°F to 0.5°F
+11390
+11120
-148°F
0
+1112°F
-1480 Temperature
-1750