Fx 3Uc -4Ad; Grounding - Mitsubishi Electric MELSEC-FX3S Series Manual

Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
FX
-4AD/FX
-4AD (4-channel Analog Input)
3U
3UC
3.4.2
FX
-4AD
3UC
If current input is
selected
If voltage input is
selected
V+, I+, ch :  represents the channel number.
*1.
Use the 2-core shielded twisted pair cable for the analog input lines, and separate the analog input
lines from the other motive power lines or inductive lines.
*2.
To use the current input, be sure to short circuit the line between the V + terminal and the I
+ terminal ( : channel number).
*3.
The SLD and "
*4.
Do not connect any lines to the "•" terminal.
3.5

Grounding

Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
PLC
equipment
Independent grounding
Best condition
• Use the following grounding wire.
FX
-4AD
3U
FX
-4AD
3UC
• The PLC grounding point should be close, and all grounding wires should be as short as possible.
B-16
PLC User's Manual - Analog Control Edition
3UC
Terminal
block
*1
V+
*2
I+
COM
SLD
*1
V+
I+
COM
SLD
*4
Class-D
grounding
" terminals are connected to each other inside.
→ For details, refer to the User's Manual - Hardware Edition of each Series.
Other
Other
PLC
equipment
Shared grounding
Good condition
2
AWG14 (2mm
)
AWG22-20 (0.3 to 0.5mm
FX
-4AD
3UC
6.8kΩ
250Ω
200kΩ
*3
6.8kΩ
250Ω
200kΩ
Other
PLC
equipment
Common grounding
Not allowed
2
)
ch
ch
3 Wiring
3.5 Grounding