Fx 3U -4Ad-Tc-Adp - Mitsubishi Electric MELSEC-FX3S Series Manual

Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
Common Items
4.4.4
FX
-4AD-TC-ADP
3U
Specifications
Number of input points
Input signal
Rated temperature range
Digital output
Resolution
Overall accuracy
Time required for
conversion
Input characteristics
Insulation method
Number of I/O points
occupied
A-48
PLC User's Manual - Analog Control Edition
3UC
Centigrade (°C)
• Type K: -100°C to +1000°C
• Type J: -100°C to +600°C
• Type K: -1000 to +10000
• Type J: -1000 to +6000
• Type K: 0.4°C
• Type J: 0.3°C
• FX
/FX
Series PLC : 200μs (Data updated every scan time.)
3U
3UC
• FX
/FX
/FX
Series PLC : 250μs (Data updated every scan time.)
3S
3G
3GC
• Type K
+10100
+10000
-110°C
0
Temperature
-1000
-1100
• Type J
+6100
+6000
-100°C
0
Temperature
-1000
-1100
• The photocoupler is used to insulate the analog input area from the PLC.
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
0 points
(This number of points is not related to the maximum number of input/output points of the PLC.)
FX
-4AD-TC-ADP
3U
4ch
Thermocouple type K or J
JIS C 1602-1995
• Type K: -148°F to +1832°F
• Type J: -148°F to +1112°F
• Type K: -1480 to +18320
• Type J: -1480 to +11120
• Type K: 0.72°F
• Type J: 0.54°F
± (0.5% for full scale +1°C)
• Type K
+1000°C
• Type J
+600°C
4 Comparison of Performance Specifications
4.4 Temperature Sensor Input
Fahrenheit (°F)
+18500
+18320
-148°F
0
+1832°F
Temperature
-1480
-1660
+11300
+11120
-148°F
0
+1112°F
Temperature
-1480
-1660