-4AD-ADP (4-channel Analog Input)
3U
3.2

Applicable Cables and Terminal Tightening Torque

Use the following cables to connect with the counterpart equipment. Terminate the cable ends as shown
below.
1. Cables
Applicable cable and tightening torque
0.3 mm
Single-wire
(AWG22 to 20)
2-wire
0.3 mm
0.3 mm
Ferrule with
(AWG22 to 20)
insulation
(Refer to the external view
sleeve
of ferrule shown in the
following figure.)
*1.
Old model name : CRIMPFOX ZA 3
*2.
Old model name : CRIMPFOX UD 6
2. Termination of cable end
To terminate the cable, treat the stranded/single-wire directly or use a ferrule with insulation sleeve.
Tighten the terminals to a torque of 0.22 to 0.25 N•m.
Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do so may cause
equipment failures or malfunctions.
• To directly terminate the end of a stranded/single-wire cable:
- Twist the end of the stranded cable so that the "barbed wires"
cannot protrude.
- Do not solder-plate the end of the cable.
• To terminate cable end using a ferrule with insulation sleeve:
If the cable sheath is too thick, it may be difficult to insert the cable into
the insulation sleeve. For this reason, select an appropriate cable while
referring to the external view.
<Reference>
Manufacturer
Phoenix Contact
*3.
Old model name : CRIMPFOX ZA 3
*4.
Old model name : CRIMPFOX UD 6
3. Tool
For tightening the terminal, use a commercially available small screwdriver
having a straight form that is not widened toward the end as shown right.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not be
able to be achieved. To achieve the appropriate tightening torque shown in
the table above, use the following screwdriver or an appropriate
replacement (grip diameter: approximately 25 mm (0.98")).
<Reference>
Manufacturer
Phoenix Contact
C-14
PLC User's Manual - Analog Control Edition
3UC
Wire size
(stranded wire/solid wire)
2
2
to 0.5 mm
2
(AWG22)×2
2
2
to 0.5 mm
Model
AI 0.5-8WH
3.2 Applicable Cables and Terminal Tightening Torque
Tightening
torque
• To connect a stranded cable, peel the cover off the cable
and then twist the core before connection.
• To connect a single-wire cable, just strip the cover off the
cable before connection.
0.22 to
• Ferrule with insulation sleeve
0.25 N•m
(recommended terminal)
AI 0.5-8WH : Manufactured by Phoenix Contact
• Caulking tool
CRIMPFOX 6
(or CRIMPFOX 6T-F
Caulking tool
CRIMPFOX 6
(or CRIMPFOX 6T-F
Model
SZS 0.4×2.5
Termination
*1
: Manufactured by Phoenix Contact
*2
: Manufactured by Phoenix Contact)
• Stranded wire/solid wire
9mm
(0.35")
• Ferrule with insulation sleeve
Insulation sleeve
2.6mm
14mm
(0.1")
(0.55")
*3
*4
)
0.4mm
(0.01")
3 Wiring
Contact area
(Crimp area)
8mm
(0.31")
The head
should be
straight.
2.5mm
(0.09")