4.3.2 Backup heater kit

Checking procedures
To perform a resistance check of the backup heater
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
INFORMATION
It is recommended to perform the checks in the listed order.
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Remove the required plate work, see
a Backup heater contactor
2 Measure the backup heater resistance as shown in the table below. Tolerance
= ± 10%.
K1M/1
K5M/13
K1M/3
K1M/5
K1M/3
K1M/5
K2M/1
K5M/13
K2M/3
K2M/5
K2M/3
K2M/5
K1M/5
K2M/1
"4.16 Plate
a
a
a
3 kW
6 kW
1~230 V
1~230 V
53 Ω
53 Ω
106 Ω
106 Ω
159 Ω
159 Ω
53 Ω
53 Ω
26.5 Ω
26.5 Ω
OL
OL
OL
OL
53 Ω
53 Ω
132.5 Ω
132.5 Ω
draft – 31/05/2022 15:53
4
|
Components
4
work" [
 202].
6 kW
9 kW
3N~400 V
3N~400 V
OL
OL
106 Ω
106 Ω
106 Ω
106 Ω
106 Ω
106 Ω
OL
OL
53 Ω
53 Ω
53 Ω
53 Ω
53 Ω
53 Ω
OL
OL
Service manual