Daikin EBLA04E V Series Service Manual page 149

Table of Contents

Advertisement

To perform a mechanical check of the compressor
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
Prerequisite: First perform an auditive check of the compressor, see
"4.7.1 Checking
procedures" [
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Before proceeding:
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10  V  DC before proceeding, see
electrical
hazards" [
2 Visually check:
▪ For oil drops around the compressor. Locate and fix as needed.
▪ Pipes for signs of damage. Replace pipes as needed.
3 Check that the compressor bolts are correctly fixed. Fix as needed.
4 Check that the compressor wire terminals cover is correctly installed and
fixed. Correct as needed.
5 Check the compressor dampers for any damage.
a
a Damper
INFORMATION
The compressor dampers may look different.
Compressor dampers are in a good
condition?
Yes
No
4
 148].
4
 254].
a
Action
Perform an electrical check of the
compressor, see
procedures" [
Replace the compressor and/or
damaged dampers, see
procedures" [
draft – 31/05/2022 15:53
4
|
Components
"To prevent
"4.7.1 Checking
4
 148].
"4.7.2 Repair
4
 153].
Service manual
149