To Connect The Backup Heater Kit To The Control Box - Daikin EWAQ006BAVP Installer's Reference Manual

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWAQ006BAVP:
Table of Contents

Advertisement

7 Installation
Backup heater
Connections to
type
backup heater power
supply
3 kW 1~ 230 V
(*3V)
F1B
L N
L N
3 kW 1~ 230 V
(*9W)
F1B
6 kW 1~ 230 V
(*9W)
L
L
N
N
6 kW 3N~ 400 V
(*9W)
F1B
9 kW 3N~ 400 V
(*9W)
L1 L2 L3
Special remark for fuses:
Special remark for terminals:
As mentioned on the table above, the connections on the terminals
X6M and X7M need to be changed to configure a backup heater.
Refer to the illustration below as a caution about handling the
terminals.
Installer reference guide
44
Connections to
terminals
X14M
1 2 3 4 5 6
During connection of the backup heater, miswiring is possible. To
X14M
detect possible miswiring on the *9W model, it is highly
recommended to measure the resistance value of the heater
1 2 3 4 5 6
elements. Depending on the different backup heater types, following
resistance values (see table below) should be measured. ALWAYS
measure the resistance on the contactor clamps K1M, K2M, and
K5M.
Example measure resistance between K1M/1 and K5M/13:
7.8.21
3 Fix the cable with cable ties to the cable tie mountings.
INFORMATION
For more information on the backup heater types, and for
how to configure the backup heater, refer to the
"Configuration" chapter of the installation manual of the
outdoor unit.
3 kW
1~ 230 V
K1M/1
K5M/13
52.9Ω
K1M/3
K1M/5
K1M/3
K1M/5
26.5Ω
K2M/1
K5M/13
K2M/3
K2M/5
K2M/3
K2M/5
52.9Ω
K1M/5
K2M/1
K1M
1 3 5 13
2 4 6 14
Ω
Ω
K5M
1 3 5 13
2 4 6 14
To connect the backup heater kit to the
control box
INFORMATION
▪ Requires
to
be
EKCB07CAV3.
EWAQ+EWYQ006+008BAVP + EK(2)CB07CAV3 +
Packaged air-cooled water chillers and packaged air to water heat
6 kW
6 kW
9 kW
1~ 230 V
3N~
3N~
400 V
400 V
52.9Ω
105.8Ω
105.8Ω
105.8Ω
158.7Ω
105.8Ω
105.8Ω
52.9Ω
105.8Ω
105.8Ω
26.5Ω
52.9Ω
52.9Ω
52.9Ω
52.9Ω
52.9Ω
52.9Ω
52.9Ω
132.3Ω
K2M
K2M
1 3 5 13
2 4 6 14
connected
to
control
box
EKMBUHCA3V3+9W1
pumps
4P492901-1 – 2017.06