Daikin EBLA04E V Series Service Manual page 182

Table of Contents

Advertisement

4
|
Components
Service manual
182
draft – 31/05/2022 15:53
LED
Description
LD2
Indication of TCP/IP
communication with the
router.
LD3
Indication of communication
with the indoor unit.
(a)
LD4
Indication of Smart Grid
activity.
(a) This LED is ONLY active for BRP069A61 (present for BRP069A62, but ALWAYS
inactive).
INFORMATION
When the LAN adapter performs a Smart Grid compatibility check, LD4 flashes.
This is NOT erroneous behaviour. After a successful check, LD4 will either stay ON
or go OFF. When it keeps flashing for more than 30 minutes, the compatibility
check failed, and NO Smart Grid operation is possible.
a LED 1: heartbeat
b LED 2: LAN communication
c LED 3: P1/P2 communication
d LED 4: smart grid control active
Behaviour
LED
ON:
communication.
LED flashing: communication
problem.
Check
communication
with
router.
LED
ON:
communication.
LED flashing: communication
problem.
Check
communication between the
LAN adapter and the unit
PCB,
"4.13.1 
Checking
procedures" [
4
 181].
LED ON: system running in
the
"Recommended
"Forced ON", or "Forced OFF"
Smart Grid operation mode.
LED OFF: system running in
the
"Normal
operation"
Smart Grid operation mode,
or
operating
in
operation conditions (space
heating/cooling,
production
of domestic hot water).
LED flashing: LAN adapter
performing a Smart Grid
compatibility check.
a
b
c
d
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
normal
TCP/IP
the
normal
the
ON",
normal

Advertisement