Backup Heater Kit - Daikin Altherma EBLQ011CAV3 Service Manual

Monobloc
Hide thumbs Also See for Altherma EBLQ011CAV3:
Table of Contents

Advertisement

Prerequisite: Turn off the respective circuit breaker of the unit and
the backup heater.
Prerequisite: Remove the required plate work, see
work" on
page 77.
1 Disconnect the wiring from the backup heater contactor
terminals.
2 Remove the screws and remove the backup heater contactors
from the switch box.
3 To
install
the
backup
procedures" on
page 42.
To install the backup heater contactors
1 Install the backup heater contactors in the switch box and fix
them using the screws.
2 Connect the wiring to the correct backup heater contactor
terminals.
Is the problem solved?
Yes
No
2.4.2

Backup heater kit

Checking procedures
INFORMATION
It is recommended to perform the checks in the listed
order.
To perform an electrical check of the backup heater
Prerequisite: Turn OFF the unit via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work.
Prerequisite: Check the circuit breaker. Reset if it has tripped.
Prerequisite: Check the backup heater thermal protector. Reset if it
has tripped. See
"2.5 Backup heater thermal protector" on
1 Turn ON the power of the unit.
INFORMATION
If the circuit breaker or the backup heater thermal protector
trips again, determine the root cause of the problem.
Something is overloading the electrical circuit or creating a
short-circuit.
2 Activate Installer on the user interface. See the installer
reference guide for the correct procedure.
3 Go to Actuator test run via the user interface.
4 Activate backup heater: step 1.
5 Activate backup heater: step 2.
6 Check the status in the Actuators menu of the user interface.
This MUST be:
▪ Backup heater: step 1 = ON
And/Or
▪ Backup heater: step 2 = ON
7 Check if the field installed circuit breaker has tripped.
8 Check if the fuse of the backup heater has tripped.
EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1
+ EK(2)CB07CAV3 + EKMBUHCA3V3+9W1
Daikin Altherma – Monobloc
ESIE18-04 – 2019.02
"2.19  Plate
heater
contactors,
see
"Repair
Action
No further actions required.
Return to
"Checking
procedures" on page 41
of the
backup heater and continue with
the next procedure.
page 48.
Did the fuse or the field
supplied circuit breaker of the
backup heater trip?
Yes
No
To perform a check of the backup heater contactors
1 First perform an electrical check of the backup heater, see
"Checking procedures" on
page 45.
2 With the Actuator test run still active, measure the voltage
between the terminals before, on and after each contactor. The
voltage measurements before, on and after each contactor
MUST be the same.
a
Backup heater contactor
Are the measured voltages of
the backup heater contactors
correct?
Yes
No
To perform an insulation check of the backup heater
1 First perform a check of the backup heater contactors, see
"Checking procedures" on
page 45.
2 Open all circuit breakers.
CAUTION
To prevent damage to the unit, all fuses MUST be opened
before using a Megger.
2 Components
Action
Replace the backup heater, see
"Repair procedures" on
page 46.
Return to
"Checking
procedures" on page 45
of the
backup heater and continue with
the next procedure.
a
a
a
Action
Return to
"Checking
procedures" on page 45
of the
backup heater and continue with
the next procedure.
Replace the specific backup
heater contactor(s), see
"Repair
procedures" on
page 46.
Service manual