Daikin EBLA04E V Series Service Manual page 319

Table of Contents

Advertisement

Field settings table
Breadcrumb
Setting name
9.I
[6-0E]
What is the maximum temperature setpoint?
9.I
[7-00]
Domestic hot water booster heater overshoot temperature.
9.I
[7-01]
Domestic hot water booster heater hysteresis.
9.I
[7-02]
How many leaving water temperature zones are there?
9.I
[7-03]
--
9.I
[7-04]
--
9.I
[7-05]
Boiler efficiency
9.I
[7-06]
HP forced OFF
9.I
[7-07]
BBR16 activation*
*BBR16 settings are only visible when the language of the user
interface is set to Swedish.
9.I
[7-09]
How much is the minimum pump PWM value.
9.I
[7-0A]
Additional zone fixed pump PWM, in case a bizone kit is installed.
9.I
[7-0B]
Main zone fixed pump PWM, in case a bizone kit is installed.
9.I
[7-0C]
Time needed by the mixing valve to turn from one side to the
other, in case a bizone kit is installed.
9.I
[8-00]
Minimum running time for domestic hot water operation.
9.I
[8-01]
Maximum running time for domestic hot water operation.
9.I
[8-02]
Anti-recycling time.
9.I
[8-03]
Booster heater delay timer.
9.I
[8-04]
Additional running time for the maximum running time.
9.I
[8-05]
Allow modulation of the LWT to control the room temp?
9.I
[8-06]
Leaving water temperature maximum modulation.
9.I
[8-07]
What is the desired comfort main LWT in cooling?
9.I
[8-08]
What is the desired eco main LWT in cooling?
9.I
[8-09]
What is the desired comfort main LWT in heating?
9.I
[8-0A]
What is the desired eco main LWT in heating?
9.I
[8-0B]
--
9.I
[8-0C]
--
9.I
[8-0D]
--
9.I
[9-00]
What is the maximum desired LWT for main zone in heating?
9.I
[9-01]
What is the mimimum desired LWT for main zone in heating?
9.I
[9-02]
What is the maximum desired LWT for main zone in cooling?
9.I
[9-03]
What is the mimimum desired LWT for main zone in cooling?
9.I
[9-04]
Leaving water temperature overshoot temperature.
9.I
[9-05]
What is the mimimum desired LWT for add. zone in heating?
9.I
[9-06]
What is the maximum desired LWT for add. zone in heating?
9.I
[9-07]
What is the mimimum desired LWT for add. zone in cooling?
9.I
[9-08]
What is the maximum desired LWT for add. zone in cooling?
9.I
[9-09]
What is the allowed LWT undershoot during cooling start-up?
9.I
[9-0A]
What is the room buffering temperature in heating?
9.I
[9-0B]
What is the room buffering temperature in Cooling?
(*1) EBLA*_(*2) EDLA*_(*3) *23V3_(*4) *2V3
Range, step
Default value
R/W
E-07 = 0
40~ 60°C, step: 1°C
60°C
E-07 = 3
40~ 75°C, step: 1°C
75°C
E-07 = 5
40~ 80°C, step: 1°C
80°C
E-07 = 7
40~ 60°C, step: 1°C
60°C
E-07 = 8
40~ 75°C, step: 1°C
75°C
R/W
0~4°C, step: 1°C
0°C
R/W
2~40°C, step: 1°C
2°C
R/W
0: Single zone
1: Dual zone
2.5
0
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
R/W
0: Disabled
1: Enabled
R/W
0: No
1: Yes
R/W
20%
R/W
20~95%, step 5%
95%
R/W
20~95%, step 5%
95%
R/W
20~300 seconds, step 5 sec
125 seconds
R/W
0~20 min, step 1 min
1 min
R/W
5~95 min, step: 5 min
30 min
R/W
0~10 hour, step: 0,5 hour
3 hour
R/W
20~95 min, step: 5 min
50 min
R/W
0~95 min, step: 5 min
95 min
R/W
0: No
1: Yes
R/W
0~10°C, step: 1°C
5°C
R/W
[9-03]~[9-02], step: 1°C
18°C
R/W
[9-03]~[9-02], step: 1°C
20°C
R/W
[9-01]~[9-00], step: 1°C
35°C
R/W
[9-01]~[9-00], step: 1°C
33°C
13
10
16
R/W ([2-
[2-0C]=2:
0C] ≠ 2)
37~70, step: 1°C
R/O ([2-
65°C
0C] = 2)
[2-0C]≠2:
37~55, step: 1°C
55°C
R/W
15~37°C, step: 1°C
25°C
R/W
18~22°C, step: 1°C
22°C
R/W
5~18°C, step: 1°C
5°C
R/W
1~4°C, step: 1°C
1°C
R/W
15~37°C, step: 1°C
25°C
R/W ([2-
[2-0C]=2:
0C] ≠ 2)
37~70, step: 1°C
R/O ([2-
65°C
0C] = 2)
[2-0C]≠2:
37~55, step: 1°C
55°C
R/W
5~18°C, step: 1°C
7°C
R/W
18~22°C, step: 1°C
22°C
R/W
1~18°C, step: 1°C
18°C
R/W
[3-07]~[3-06]°C, step: 0,5°C
23°C
R/W
[3-09]~[3-08]°C, step: 0,5°C
23°C
Installer setting at variance with
default value
Date
Value
4P685235-1 - 2022.03