Field settings table
Breadcrumb
Setting name
9.1.8.1
[2-0D]
Emitter type
9.1.8.3
Setpoint mode
9.1.8.4
Schedule
9.1.9
[0-00]
Leaving water value for high ambient temp. for LWT add zone
heating WD curve.
9.1.9
[0-01]
Leaving water value for low ambient temp. for LWT add zone
heating WD curve.
9.1.9
[0-02]
High ambient temp. for LWT add zone heating WD curve.
9.1.9
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
9.1.A
[0-04]
Leaving water value for high ambient temp. for LWT add zone
cooling WD curve.
9.1.A
[0-05]
Leaving water value for low ambient temp. for LWT add zone
cooling WD curve.
9.1.A
[0-06]
High ambient temp. for LWT add zone cooling WD curve.
9.1.A
[0-07]
Low ambient temp. for LWT add zone cooling WD curve.
└─ Tank
9.1.B.1
[6-0D]
Heat up mode
9.1.B.2
[6-0A]
Comfort setpoint
9.1.B.3
[6-0B]
Eco setpoint
9.1.B.4
[6-0C]
Reheat setpoint
9.1.B.5
[6-08]
Reheat hysteresis
└─ Domestic hot water
9.2.1
[E-05]
Domestic hot water
[E-06]
[E-07]
9.2.2
[D-02]
DHW pump
9.2.4
[D-07]
Solar
└─ Back up heater
9.3.1
[E-03]
BUH type
9.3.2
[5-0D]
Voltage
9.3.3
[4-0A]
Configuration
9.3.4
[6-03]
Capacity step 1
9.3.5
[6-04]
Additional capacity step 2
9.3.6
[5-00]
Equilibrium: Deactivate backup heater (or external backup heat sou
9.3.7
[5-01]
Equilibrium temperature
9.3.8
[4-00]
Operation
4P685235-1 - 2022.03
Range, step
Default value
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
R/W
0: No
1: Yes
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
[2-0C]=0
25°C
[2-0C]=1
35°C
[2-0C]=2
40°C
R/W
[9-05]~[9-06]°C, step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
60°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0
18°C
[2-0C]=1
7°C
[2-0C]=2
18°C
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0
22°C
[2-0C]=1
15°C
[2-0C]=2
22°C
R/W
25~43°C, step: 1°C
35°C
R/W
10~25°C, step: 1°C
20°C
R/W
0: Reheat only
1: Schedule + reheat
2: Schedule only
R/W
30~[6-0E]°C, step: 1°C
60°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
2~20°C, step: 1°C
10°C
R/W
E-05=0
No DHW
E-07 = 0
EKHWS/E, small volume
E-07 = 3
EKHWS/E, big volume
E-07 = 5
EKHWP/HYC
E-07 = 7
3rd party, small coil
E-07 = 8
3rd party, big coil
R/W
0: No DHW pump
1: Instant hot water
2: Disinfection
3: Circulation
4: Circulation and disinfection
R/W
0: No
1: Yes (DHW)
R/O (*3)
0: No heater (*4)
R/W (*4)
1: External heater
2: 3V (*3)
R/O(*3)
0: 230V, 1~ (*3)
R/W(*4)
1: 230V, 3~
2: 400V, 3~
R/W
0: 1
1: 1/1+2
2: 1/2
3: 1/2 + 1/1+2 in emergency
R/W
0~10kW, step: 0,2kW
0kW (*4)
3kW (*3)
R/W (*4)
0~10kW, step: 0,2kW
R/O (*3)
0kW (*3)
R/W
0: No
1: Yes
R/W
-15~35°C, step: 1°C
0°C
R/W
0: Restricted
1: Allowed
2: Only DHW
Installer setting at variance with
default value
Date
Value
(*1) EBLA*_(*2) EDLA*_(*3) *23V3_(*4) *2V3