2.3 Status display masks

The various status display masks provide:
a complete overview regarding the status of the unit;
useful information for the unit maintenance operator.
In the main loop there are, in addition to the main mask and the Temperature Probes mask, only the masks that allow you to
view the status of the various functions active on the unit, if any. This makes the main loop dynamic and quick to consult thanks
to the reduced number of masks visible at any time.
The "Unit" menu contains all the masks that allow you to view the status of the various operating devices of the unit. It is
therefore static and complete, and intended for occasional consultation.
The Temperature Probe mask can be found both in the main loop and the "Unit" menu. There is a shortcut that allows to switch
from one to the other and vice versa simply by pressing [ENTER].
The "In/Out" menu allows to control:
the status of the input and output values of the controller board and the I/O expansion boards;
the Modbus addresses used by active devices with Modbus communication.
The "Log" menu allows you to view the alarm log. See the chapter "Event Log" for further information.
The following paragraphs list the status display masks belonging to the various menus.
Press the [UP] and [DOWN] keys to move from one mask to another.
To return to the menu selection list or main mask, press the [ESC] key.
2.3.1

Main loop

Mask of the terminal
13:51 06/04/20
26.1C
57.0%
OFF
Active Functions
Waiting for Regulation
to Start
Temperature Probes
24.0°C
15.0°C
35.0°C
Go to Unit menu
REQUEST STATUS
Step req: 11 Sent: 11
Cooling request: 100%
Waiting:
NONE
Waiting time: 000sec
Version 38
Main mask. Displays the type of unit, the current date and time, the temperature and
humidity currently used for adjustment, and the power-on status of the unit.
For more information see the "Main mask" section.
Display of the active functions in the unit.
For more information see the "Active Functions Mask" section.
Visible only when certain functions are active
Display of the values of the temperature probes.
Return temperature probe
Delivery temperature probe
External temperature probe
Pressing the [ENTER] key switches to the Temperature Probes mask in the "Unit" menu.
This shortcut provides quick access to the display masks of the unit's internal devices.
Mask displaying the requests of cold and steps sent to the PCA-IF013B-E card
It also shows if the system is waiting for the expiry of a time delay before sending the steps
to the Master PAC-IF013B-E card:
[NONE] No delay
[SHORT WAIT] Short delay (300s / 5min)
[LONG WAIT] Long delay (600s / 10min)
[CHANGING MODE] Cycle inversion/mode change (120 s / 2min)
[MIN T.OFF] Minimum Off (120s / 2min)
Information visible only with S-MEXT units.
Description