Mitsubishi Electric Evolution+ s-MEXT Technical Manual page 56

Table of Contents

Advertisement

Mask of the terminal
Regulations
--------------- P20.98
Max Increase N.Zone
for Tsupply reg:03.0°C
--------------- P20.99
Max Decrease N.Zone
for Tsupply reg:03.0°C
Regulations
--------------- P20.55
Time for reduction of
Neutral Zone:
05min
--------------- P20.64
FC valve position for
reduct in N.Zone:80%
Regulations
--------------- P20.56
Supply temp. setpoint
lower limit:
10.0°C
--------------- P20.57
Supply temp. setpoint
upper limit:
25.0°C
Regulations
--------------- P20.71
T+H limits alarm on
unit OFF enable:
Y
--------------- P20.72
T+H limits alarm delay
after unit ON:
600s
Regulations
--------------- P20.73
Safety Reduction Load
(LP) enable:
Regulations
--------------- P20.74
Circuit 1 SRL (LP)
setpoint:
7.5bar
--------------- P20.75
Circuit 1 SRL (LP)
differential:
1.0bar
Regulations
--------------- P20.76
Circuit 1 SRL (LP)
step time:
05min
--------------- ------
----------------------
Regulations
--------------- P20.82
Amount of remote T+H
probes enabled:
4
Version 38
Maximum Neutral Switch-On Zone for increasing the resources for delivery air
control.
Maximum Neutral Switch-Off Zone for decreasing the resources for delivery air
control.
Visible only if the unit is adjusted according to the delivery air.
Time for reduction from Maximum to Minimum Neutral Zone for delivery air control.
Opening of the Free Cooling valve for controlling reduction of resources in the
Neutral Zone.
Visible only if the unit is adjusted according to the delivery air.
Lower limit of the setpoint for delivery air control.
Upper limit of the setpoint for delivery air control.
Visible only if the unit is adjusted according to the delivery air.
Enable room temperature limit control with the unit OFF.
Delay before activation of the ambient temperature limit alarms after the fan is
activated.
Enable the Safety Reduction Load Low Pressure (SRL LP) function.
N
Low pressure setpoint for activation of the SRL LP function for circuit 1.
Low pressure differential for deactivation of the SRL LP function for circuit 1.
Visible only if the relevant function is enabled.
Time between each frequency reduction step with SRL LP function active for circuit
1.
Maximum number of frequency reduction steps with SRL LP function active for
both circuits.
Visible only if the relevant function is enabled.
Parameter for indicating the number of remote serial TH probes connected to the
unit.
Description
Par.N.
20.98
20.99
20.55
20.64
20.56
20.57
20.71
20.72
20.73
20.74
20.75
20.76
20.82
56