Mitsubishi Electric Evolution+ s-MEXT Technical Manual page 41

Table of Contents

Advertisement

Icon
High Temperature pLAN
Rescue Activated
Low Temperature pLAN
Rescue Activated
High Humidity pLAN
Rescue Activated
Low Humidity pLAN
Rescue Activated
Hot Spot Protection
Activated
Cold Spot Protection
Activated
Active Fan on Stand-by
Activated
PERIODIC CHECK
NOTE:
All the active functions of the unit are displayed in the same mask (with the flashing of various icons).
Version 38
Function
High temperature pLAN
rescue active.
Low temperature pLAN
rescue active.
High humidity pLAN
rescue active.
Low humidity pLAN
rescue active.
Hot Spot protection for an
active pLAN network.
Cold Spot protection for
an active pLAN network.
Active Fan function on
Stand-by active.
Regular control
Meaning
The unit is in pLAN rescue mode due to the high
temperature limit being exceeded.
The unit is in pLAN rescue mode due to the low
temperature limit being exceeded.
The unit is in pLAN rescue mode due to the high humidity
limit being exceeded.
The unit is in pLAN rescue mode due to the low humidity
limit being exceeded.
The unit considers its local temperature instead of the
average temperature to control the Hot Spot concerned.
The unit considers its local temperature instead of the
average temperature to control the Cold Spot concerned.
The unit is on standby but the fan continues to run at a
set speed.
The unit forces the cooling demand sent to the PAC-IF
cards to minimum and keeps ventilation at maximum to
help prevent the formation of ice on the piping.
41