Mitsubishi Electric Evolution+ s-MEXT Technical Manual page 63

Table of Contents

Advertisement

Mask of the terminal
Settings
--------------- P22.85
Fire/smoke event type:
A-M
Settings
--------------- P22.88
External dumper alarm
enable:
--------------- ------
----------------------
Settings
--------------- P22.94
Low supply temp.
alarm setpoint:
10°C
--------------- P22.95
High supply temp.
alarm setpoint:
32°C
Settings
--------------- P22.96
Low supply humidity
alarm setpoint:
30%RH
--------------- P22.97
High supply humidity
alarm setpoint:
80%RH
Settings – KIPlink
Status:Offline
WiFi Network SSID:
KIPlink_032000000
IP Address:
000.000.000.000
Channel: WiFi
Settings – KIPlink
Module type:
Master-EthOFF-WiFiON
Settings – KIPlink
Ethernet channel:
IP: 192.168.030.001
Sub:255.255.255.000
Gw: 000.000.000.000
Settings – KIPlink
WiFi channel:
IP: 192.168.030.001
Sub:255.255.255.000
Gw: 000.000.000.000
Settings – KIPlink
Network Info
SSID master:
KIPlink_032000000
IP master:
192.168.030.001
KIPlink ID: 01
Version 38
Parameter for setting the type and reset of the Fire/Smoke event.
Visible only if smoke/fire sensor management is enabled.
Enable the control of the external damper alarm (not controlled by the logic).
N
Delay time before activation of the external damper alarm.
Low air delivery temperature alarm setpoint.
High air delivery temperature alarm setpoint.
Low air delivery humidity alarm setpoint.
High air delivery humidity alarm setpoint.
Display of the status and main information of the KIPlink module.
Display of the type of KIPlink module.
Display of information on the KIPlink Ethernet network.
Display of information on the KIPlink Wi-Fi network.
Display of the main information of the Priority module of the KIPlink network.
Description
Par.N.
22.85
22.88
22.94
22.95
22.96
22.97
63