[P900] Clock Menu - Mitsubishi Electric Evolution+ s-MEXT Technical Manual

Table of Contents

Advertisement

Mask of the terminal
Setpoint
--------------- P50.07
Dehumdific. Setpoint
with LAN limits: 75%RH
--------------- P50.08
Humdific. Setpoint
with LAN limits: 35%RH
Setpoint
--------------- P50.09
Min return temperature
for dehumid OFF:18.0°C
Setpoint
--------------- P50.14
Temp. setpoint for
fan regulation with
fan reg. funct.
enabled:
24.0°C
Setpoint
--------------- P50.15
Treturn setpoint for
fan regulation with
return temp. fan reg.
funct. Enabled
with LAN limits:30.0°C
2.5.26

[P900] Clock Menu

Accessible from: "Main" group.
Mask of the terminal
Clock
Clock
Clock card
not installed
Clock
Clock Config.
Date
Time
22/11/18
13:58
Clock
Time bands
not enabled.
See Scheduler menu
Version 38
Dehumidification setpoint during LAN out of range.
Humidification setpoint during LAN out of range.
Parameter for minimum room temperature and dehumidifier off.
Visible only on units with at least one direct expansion circuit on which the
dehumidification function is enabled.
Temperature setpoint for fan control.
Return temperature setpoint for adjustment of the fan based on the return
temperature during LAN out of range.
Access mask to "Clock" menu.
Mask indicating the lack or damage to the clock board.
Current date and time setting.
Indicates that the time bands have been set correctly, though they are not enabled.
To enable them, go to the "Scheduler" menu of the "User" group.
Description
Description
Par.N.
50.07
50.08
50.09
50.14
50.15
Par.N.
91