Code
Display description
Event
PAC-IF Client
188
offline alarm
Event
PAC-IF Server1
189
offline alarm
Event
I/O Expansion Board 4
191
Offline
Event
I/O Expansion Board 1
192
Offline
Event
I/O Expansion Board 2
193
Offline
Event
I/O Expansion Board 3
194
Offline
Event
Humidifier Board
195
Offline
Event
Fan 5
196
Generic Alarm
Event
Energy Analyzer 1
199
Offline
Event
Energy Analyzer 2
200
Offline
Event
Sup. T+H Probe
307
Failed/Disconnected
Event
Sup. Temp.T+H Probe
308
Failed/Disconnected
Event
Sup. Hum. T+H Probe
309
Failed/Disconnected
Event
Circ. 1 LP Switch
320
Triggered
Version 38
Details
A188
PAC-IF Client disconnection alarm (Mr.
Slim connection board)
A189
PAC-IF Server 1 disconnection alarm (Mr.
Slim connection board)
I/O expansion 4 disconnection alarm
A191
(serial connection).
Visible only if the unit requires expansion.
I/O expansion 1 disconnection alarm
A192
(serial connection).
Visible only if the unit requires expansion.
I/O expansion 2 disconnection alarm
A193
(serial connection).
Visible only if the unit requires expansion.
I/O expansion 3 disconnection alarm
A194
(serial connection).
Visible only if the unit requires expansion.
CPY dehumidifier board disconnection
A195
alarm (serial connection).
Visible only if internal control humidifier is
present.
Generic problem on fan 5.
See the third row for details on the
A196
problem.
Visible only if the unit has at least one EC
fan.
Network analyser disconnection alarm
A199
(serial connection).
Visible only if the network analyser is
enabled.
Network analyser 2 disconnection alarm
A200
(serial connection).
Visible only if the network analyser 2 is
enabled.
Delivery T+H probe disconnection alarm
A307
(serial connection).
Visible only if the probe is enabled.
Delivery T+H probe temperature sensor
A308
fault.
Visible only when the Delivery T+H probe
is present.
Delivery T+H probe humidity sensor fault.
A309
Visible only when the Delivery T+H probe
is present.
A320
Circuit 1 low pressure alarm from pressure
switch.
Event
Reset Time Position Action
Time
A
A
P
A
A
P
A
A
U
A
A
U
A
A
U
A
A
U
A
A
U
A
A/M
U
A
A
U
A
A
U
A
A
U
A
A
U
A
A
U
A
A->M
CI
CI
CI
FN
FN
FN
FN
HU
CI/-
FN
FN
NO
NO
NO
CI
124