Preparation for installing the unit
The transformer low-voltage side must withstand an earth fault current at three times the grid frequency
in the range of 10 Arms/MVA.
The dimensioning of the transformer must take into account:
The power cycles of the photovoltaic application.
The voltage and frequency characteristics (and their tolerances) of the connection point.
The regulations of the country where it is to be installed.
The environmental factors of the installation location (temperature, humidity, altitude, etc.).
The transformer is an essential part of the installation; its features must be taken into account when
designing the necessary downstream protections.