Preparation for installing the unit
•
The transformer low-voltage side must withstand an earth fault current at three times the grid frequency
in the range of 10 Arms/MVA.
•
The dimensioning of the transformer must take into account:
•
The power cycles of the photovoltaic application.
•
The voltage and frequency characteristics (and their tolerances) of the connection point.
•
The regulations of the country where it is to be installed.
•
The environmental factors of the installation location (temperature, humidity, altitude, etc.).
•
The transformer is an essential part of the installation; its features must be taken into account when
designing the necessary downstream protections.
ABZ2011IQM01_F - Installation and Operation Manual