Gauge
20 A
15 A
12 A
To replace the fuses, proceed as indicated below:
1.
Remove voltage as explained in section
2.
Wait 5 minutes for the voltage to discharge.
3.
Open the unit's lower compartment.
4.
Check that there is no voltage on the unit.
5.
Remove the polycarbonate guard.
6.
Remove the fuse using the extractor.
7.
Take the fuse out of the extractor and check it. Replace it if necessary, and put the new fuse in the
extractor.
8.
Reinsert the extractor into the fuse holder.
9.
Place the polycarbonate guard.
10. Close the unit's lower compartment.
11. Proceed to connect and power it.
DANGER
The unit may be damaged if the fuse is inserted into the power card clips incorrectly.

14.5. Changing the fans

This inverter is equipped with several fans which are necessary for its proper cooling.
The estimated life of these fans depends mainly on the ambient temperature conditions. In average operating
conditions it is estimated that they could last 10 years.
It is recommended to replace the fans after this time.
112
Manufacturer
Mersen
Bussmann
Littelfuse
Mersen
Bussmann
Littelfuse
Mersen
Bussmann
Littelfuse
"13. Shutting down the
Manufacturer reference
HP15M20
PV-20A10F85L
SPXV020
HP15M15
PV-15A10F85L
SPXV015
HP15M12
PV-12A10F85L
SPXV012
unit".
ABZ2011IQM01_F - Installation and Operation Manual
Maintenance

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ingecon sun 3play

Table of Contents