2.9. Specification table

DC inputs
Recommended power range of PV array
Maximum input voltage
(1)
MPP voltage range
(2)
Operating voltage range
Minimum voltage for Pnom
Maximum short circuit current
Maximum inverter backfeed current to the PV array.
MPPT number
Number of strings (STD version / PRO version)
Maximum input current
(3)
Maximum input current per string
AC output
Nominal power at 25 ºC / 40 ºC / 50 ºC
Maximum continuous power
Maximum current at 25 ºC / 40 ºC / 50 ºC
Inrush current
Maximum output fault current
Maximum output overcurrent protection
Rated voltage
Configurable rated voltages
Nominal frequency
Power factor
Adjustable power factor
(4)
THD
(5)
Type of grid
Performance
Maximum efficiency
Euroefficiency
General data
Cooling system
Air flow
Weight (STD version / PRO version)
Dimensions (height x width x depth)
Stand-by consumption
(4)
Night consumption
Operating temperature
Relative humidity (without condensation)
Maximum altitude of the installation
Protection class
Durability
Markings
RCD
EMC and safety regulations
Grid connection regulations
The inverter does not start operating until V
(1)
1) V
depends on the grid voltage (V
mpp.min
20 A.
Extended setting range for nominal operating points.
(4)
70
113 ~
95 ~ 136 kWp
162.5 kWp
570 ~ 850 V
685 ~ 1000 V
570 ~ 1450 V
685 ~ 1450 V
570 V
685 V
92.8 / 85.9 /
111.4 / 103.1 /
83.8 kW
100.6 kW
92.8 kW
111.4 kW
400 V
480 V
EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 61000-3-2, EN 61000-3-3, EN 61000-
3-11, EN 61000-3-12, EN 62109-1, EN 62109-2, IEC62103, EN 50178, FCC Part 15, IEC60068-2-1:2007,
IEC60068-2-2:20007, IEC60068-2-14:2009, IEC60068-2-30:2005, IEC62116, IEC61683 and EN50530
DIN V VDE V 0126-1-1, Arrêté du 23 avril 2008, EN 50438, EN 50439, EN 50549, CEI 0-21, CEI 0-16
VDE-AR-N 4105:2011-08, G59/3, P.O.12.3, AS4777.2, BDEW, IEC 62116, IEC 61727, UNE 206007-1, ABNT
NBR 16149, ABNT NBR 16150, Brazilian Grid Code, South African Grid Code, Chilean Grid Code, DEWA 2.0,
Jordanian Grid Code, Thailand MEA & PEA requirements
 < 1450 V.
V
is for nominal conditions (V
(2)
DC
mpp.min
), according to V
= 1.44* V
AC
mpp.min
For rated PAC and voltage according to IEC 61000-3-4.
(5)
160TL
141 ~ 203 kWp
148 ~ 213 kWp
1500 V
860 ~ 1250 V
900 ~ 1250 V
860 ~ 1450 V
900 ~ 1450 V
860 V
900 V
250 Adc
1.7 kA
1
1 / 20
168 Adc
20 A
139.3 / 128.9 /
146.2 / 135.3 /
125.8 kW
132 kW
139.3 kW
146.2 kW
134 / 124 / 121 A
<134 Arms 60ms
<220 Arms 160 ms
160 Arms
600 V
630 V
400 / 480 / 600 / 630 / 650 / 690 V
50 / 60 Hz
1
Yes. 0.8 ~ 1
<3%
TT, TN, IT
99.1%
98.7%
Forced ventilation
570 m
/h
3
75 / 78 kg
905 x 720 x 315 mm
20 W
1 W
-25 ºC ~ 60 ºC
0 ~ 100%
4000 m
IP65 / NEMA 4
C5-H
CE
1000 mA
 = 1 per unit and the power factor is
AC
.
In the PRO version the maximum current per string is
(3)
AC
ABZ2011IQM01_F - Installation and Operation Manual
Unit description
153.5 ~
162 ~
220 kWp
233.5 kWp
928 ~ 1250 V
985 ~ 1250 V
928 ~ 1450 V
985 ~ 1450 V
928 V
985 V
150.9 / 139.6 /
160.1 / 148.2 /
136.2 kW
144.6 kW
150.9 kW
160.1 kW
650 V
690 V